3 terminal configuration, 2 technical data, 1 register overview – BECKHOFF KL6071 User Manual
Page 5

Terminal configuration
KL6071
3
2.2 Technical data
Product name
KL6071
Cut off frequency
10 kHz
Current consumption from K-Bus
typically 50 mA
Electrical isolation
500 V
rms
(K-Bus / field voltage)
Bit width in the input process image
5 Byte input data, 1 status byte
Bit width in the output process image
5 Byte output data, 1 control byte
Weight
app. 60 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration / Shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance burst / ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
any
Type of protection
IP20
3 Terminal configuration
3.1 Register overview
Register
Comment
Default value
R/W
Storage medium
R0
reserved
0x0000
R
...
...
...
...
...
R5
reserved
0x0000
R
R6
Diagnose-Register - not used
0x0000
R
R7
Command register - not used
0x0000
R
R8
Terminal type
6071
R
ROM
R9
Firmware-Version
0x????
R
ROM
R10
Multiplex shift register
0x0130
R
ROM
R11
Signal channels
0x0130
R
ROM
R12
minimum data length
0x3030
R
ROM
R13
Data structure
0x0000
R
ROM
R14
reserved
0x0000
R
R15
Alignment register
variable
R/W
RAM
R16
Hardware version
0x????
R/W
SEEROM
R17
reserved
0x0000
R/W
SEEROM
...
...
...
...
...
R30
reserved
0x0000
R/W
SEEROM
R31
Code-Wort-Register
variable
R/W
RAM
R32
Feature-Register
0x0000
R/W
SEEROM
R33
reserved
0x0000
R/W
SEEROM
...
...
...
...
...
R63
reserved
0x0000
R/W
SEEROM