Troubleshooting

Troubleshooting

Please also refer to chapter

General Notes

.

Pixel errors

Note

Pixel errors in the TFT display are production-caused and represent no
complaint-reason!


Fault correction

Fault Cause Measures

The Control Panel shows no
function when the Industrial PC has
been started

No power supply to Control Panel

Cable not connected

Check power supply cable

1. Correctly connect cable
2. Call Beckhoff Service

The Industrial PC does not boot
fully

Hard disk damaged (e.g. by
switching off while software running)

Setup settings are incorrect

Other cause

1. Boot with boot diskette
2. Start SCANDISK

Check the setup settings

Call Beckhoff Service

Computer boots, software starts,
but control does not operate
correctly

The cause of the error is in the
software or in parts of the
equipment outside the control panel

Call the manufacturer of the
machine or the software

Floppy disk or CD access error

Faulty drive

Call Beckhoff Service

The Control Panel has only partial
function, or only functions some of
the time, for instance the picture is
dark or absent

Defective components in control
panel

Call Beckhoff Service.

USB error while USB access via
TwinCAT

Cycle time in TwinCAT set to 10 ms Change cycle time to 50 ms

CP66xx

17