Troubleshooting

Troubleshooting

Please also refer to chapter

General Notes

.

i

Note

Pixel errors in the TFT display are production-caused and represent
no complaint-reason!


Fault correction


Fault Cause Measures
The Control Panel shows no
function when the Industrial PC has
been started

No power supply to Industrial PC

CP-Link-cable connected not or
exchanged



Check power supply cable

1. Correctly connect CP-

Link-cable: Put the plug
with the red marking into
the socket with the red
point.

2. Call Beckhoff Service

The Industrial PC does not boot
fully

Floppy disk in the drive


Hard disk damaged (e.g. by
switching off while software running)

Setup settings are incorrect

Other cause

Remove floppy disk and
press any key

1. Boot with boot diskette
2. Start SCANDISK

Check the setup settings

Call Beckhoff Service

Computer boots, software starts,
but control does not operate
correctly

The cause of the error is in the
software or in parts of the
equipment outside the control panel

Call the manufacturer of the
machine or the software

Floppy disk access error

Faulty disk

Faulty disk drive

Check disk in another drive

Call Beckhoff Service

The control panel only exhibits
partial function, or only some of the
time - e.g., no or dark picture,
although disk drive operates when
switched on

Faulty fluorescent bulb in the
display


Defective components in control
panel

Replace fluorescent tube in
the display in accordance
with description

Call Beckhoff Service