beautypg.com

Connections – BECKHOFF CX9000 User Manual

Page 18

background image

Product overview

16

Embedded PC

Connections

The system is supplied with power via the integrated power supply. This is wired as follows:

The basic module is powered via the upper connectors with 24 V DC. The terminal bus can be supplied via the lower
connections.

UL requirements

Danger

For the compliance of the UL requirements the CX-Controllers should only be supplied

by a 24 V

DC

supply voltage, supplied by an isolating source and protected by means of a

fuse (in accordance with UL248), rated maximum 4 Amp.

by a 24 V

DC

power source, that has to satisfy NEC class 2.

A NEC class 2 power supply shall not be connected in series or parallel with another
(class 2) power source!

These UL requirements are valid for all supply voltages of the CX-Controllers!