Outputs, Resistive ratings, Inductive ratings – Basler Electric BE1-60 User Manual
Page 14: Shock, Vibration, Dielectric strength, Surge withstand capability, Radio frequency interference (rfi), Fast transient, Impulse
![background image](https://www.manualsdir.com/files/773878/content/doc014.png)
1-6
BE1-60 General Information
9170700990 Rev D
Outputs
Resistive Ratings
120 Vac:
Make, break, and carry 7 Aac continuously
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
and break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3
Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Vibration
Withstands 2 G in each of three mutually perpendicular axes, swept over the range of 10 to 500 Hz for a
total of six sweeps, 15 minutes each sweep.
Dielectric Strength
Complies with IEC 60255-5 and IEEE C37.90 one-minute dielectric (high potential) tests as follows:
All circuits to ground:
2121 Vdc
Input to output circuits:
1500 Vac or 2121 Vdc
Surge Withstand Capability
Qualified to IEEE C37.90 (transient immunity and radiated susceptibility), IEC 60255-5 (impulse
requirements), and IEC60255-5/6 (surge requirements).
Radio Frequency Interference (RFI)
Type tested using a 5 W, hand-held transceiver in the ranges of 144 and 440 MHz with the antenna
placed within 6 inches (152 millimeters) of the relay.
Fast Transient
Qualified to IEEE C37.90.
Impulse
Qualified to IEC 60255-5.
Temperature
Operating: –40
°C to 70°C (–40°F to 158°F)
Storage: –65
°C to 100°C (–85°F to 212°F)
UL Recognition
Recognized per Standard 508, UL file number E97033. Note: Output contacts are not UL-recognized for
voltages greater than 250 V.
GOST-R
Gost-R certified No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of
Russia. Issued by accredited certification body POCC RU.0001.11ME05.
Weight
14.25 lb (6.46 kg) maximum
Case Size
S1 (Refer to Section 4, Installation for case dimensions.)