Basler Electric BE3-81O User Manual
Instructions

www.basler.com
+1 618.654.2341 (USA)
Model
BE3-81O, BE3-81U,
and BE3-81O/U
INTRODUCTION
BE3 frequency relays provide frequency monitoring and 
protection in both single- and three-phase systems. They 
are used in applications such as utility mains failure, 
regulation of power supplies, and to protect generators 
against over or underspeed. Underfrequency, 
overfrequency, and combined under/overfrequency units are 
available. BE3 frequency relays operate when the 
adjustable trip point is reached. A reset control is provided 
with an adjustment of 0.3 to 3.0% on 50 or 60 hertz units 
and 3 to 30% on 400 hertz units. Reset ensures that the 
measured parameter returns to the percent set above or 
below the trip point before the relay returns to the original 
state. On overfrequency units, the output relay energizes 
when the input signal exceeds the trip point. On 
underfrequency units, the output relay de-energizes when 
the input signal goes below the trip point. A red LED 
indicates the state of the relay. A green LED indicates the 
condition of the power supply. 
SPECIFICATIONS
Operating Power
All units are self powered.
Nominal Voltage:
120 Vac, 240 Vac, 380 Vac, 
or 480 Vac 
Frequency:
50 Hz, 60 Hz, or 400 Hz
Burden:
<2.5 VA per phase
Overload:
1.25 times nominal continuously. 
2 times nominal for 3 s. 
Setpoint
Over/Underfrequency Set Range
50 Hz Nominal:
Adjustable 40 to 60 Hz
60 Hz Nominal:
Adjustable 50 to 70 Hz
400 Hz Nominal:
Adjustable 360 to 440 Hz
Over/Underfrequency Reset Range
50 Hz Nominal:
Adjustable 0.3 to 3.0 Hz
60 Hz Nominal:
Adjustable 0.3 to 3.0 Hz
400 Hz Nominal:
Adjustable 3.0 to 30 Hz
Setpoint range accuracy is
±3%.
Repeatability
Greater than 0.5% of full span
Operating Time
200 ms typical
Output
Relay Type:
D.P.D.T.
AC Rating:
250 V, 5 A, non-resistive, 
1,200 VA 
DC Rating:
125 V, 1 A, resistive, 120 W
Mechanical Life:
5 million operations
Temperature
Operating Temperature:
0°C (32°F) to 60°C (140°F)
Functional Temperature: –25°C (–13°F) to 70°C (158°F)
Storage Temperature:
–40°C (–40°F) to 70°C (158°F)
Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity:
95% non-condensing
Physical
Mounting:
DIN rail 1.38” by 0.29” (35 mm by 
7.5 mm) 
Case:
Complies with IEC 529, DIN 
40050, BS 5490 
Case Material:
Complies with UL 94VO
Weight
Single Function:
0.88 lb (0.4 kg)
Multiple Function:
1.32 lb (0.6 kg)
Size
Single Function:
2.17” wide (55 mm)
Multiple Function:
3.93” wide (100 mm)
Agency
cULus listed to UL 508 and CSA C22.2 No. 14
CE compliant
GOST-R certified per the relevant standards of Gosstandart 
of Russia 
OPERATION
BE3-81O and BE3-81U frequency relays have two user-
adjustable controls marked SET and RESET. The BE3-
81O/U has four controls: UNDER SET, OVER SET, UNDER 
RESET, and OVER RESET. Each SET control adjusts a 
relay trip point. An overfrequency trip causes the relay 
output to energize when the frequency rises above the SET 
threshold. An underfrequency trip causes the relay output to 
de-energize when the frequency decreases below the SET 
threshold. Refer to the setpoint specifications for 
overfrequency and underfrequency adjustment ranges. The 
RESET control adjusts the difference between the nominal 
input frequency and the reset frequency. An overfrequency 
reset occurs when the frequency decreases below the 
RESET setting. The overfrequency RESET setting is set as 
the percentage above F
nom
where the relay will reset. An
underfrequency reset occurs when the frequency increases 
above the RESET setting. The underfrequency RESET 
setting is set as the percentage below F
nom
where the relay
will reset. Refer to the setpoint specifications for the 
underfrequency and overfrequency RESET setting ranges. 
Setting Example
A BE3-81O relay with a nominal input rating of 60 Hz has 
the following settings: 
•
SET - 65 Hz
•
RESET - 2 Hz
Publication
9321500990
Revision
C
Instructions
Date
04/14
Copyright
2014
