Output contacts, Temperature, Type tests – Basler Electric BE1-64F User Manual
Page 10
![background image](https://www.manualsdir.com/files/773830/content/doc010.png)
Trip Function:
5,000
Ω, ±200 Ω
Pre-Alarm Function:
20,000
Ω, ±1,000 Ω
Figure 1-1. Sensitivity Characteristic
Output Contacts
Type:
Form A, B
Functions:
Ground Trip, Pre-Alarm, Power Fail
Resistive Ratings
120/240 Vac:
Make 30 Aac for 0.2 s, carry 7 Aac continuously, and break 7 Aac
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.1 Adc
Inductive Ratings
120/240 Vac, 125/250 Vdc:
Make and carry 30 A for 0.2 s, carry 7 A continuously, and
break 0.3 A (L/R = 0.04)
Contact Configurations
Ground Trip:
Form A, close on ground trip condition
Pre-Alarm:
Form A, close on pre-alarm condition
Power Fail:
Form B, close on loss of operating power
Terminal Assignments
Ground Trip:
A6, A7
Pre-Alarm:
A4, A5
Power Fail:
A8, A9
Temperature
Operating:
–40 to 70
°C (–40 to 158°F)
Storage:
–40 to 85
°C (–40 to 185°F)
Type Tests
Vibration:
IEC 255-21-1
Shock:
IEC 255-21-2
Surge Withstand Capability:
IEEE C37.90.1-1989
Radio Interference:
IEC 61000-4-3
Electrostatic Discharge:
IEC 255-22-2
Isolation:
Power, Block inputs withstand 1,500 Vac for one minute. Output contact
sets withstand 2,000 Vac for one minute. Field connection tested to
IEEE 421.3.
0
100
200
300
400
500
600
700
800
900
0
100
200
300
400
500
600
700
R
el
ay
S
en
si
ti
v
it
y
in
k
-ohm
s
DC Fault Voltage
Typical Sensitivity
Alarm
Trip
1-2
BE1-64F General Information
9367200990 Rev B