Table 2. Sensing Input Ranges
TAP
Range
Plate
or
Pickup
TAP Selector
Current Sensing
Terminals
A
B
C
D
E
F
G
H
I
J
ØA
ØB
ØC
N
Sensing Input Range 1, Single-Phase
*
HIGH
2.25
3.00 4.50 5.25 6.75
7.50 9.00 9.75
11.25
12.00
8,7
—
—
—
LOW
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
9,7
—
—
—
Sensing Input Range 1, Three-Phase
*
HIGH
2.25
3.00 4.50 5.25 6.75
7.50 9.00 9.75
11.25
12.00
8,7
14,15 17,18
—
LOW
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
9,7
13,15 16,18
—
Sensing Input Range 1, Two-Phase-and-Neutral
*
HIGH
2.25
3.00 4.50 5.25 6.75
7.50 9.00 9.75
11.25
12.00
8,7
—
14,15 17,18
LOW
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
9,7
—
13,15 16,18
Sensing Input Range 2, Three-Phase-and-Neutral
Phase
or
Neutral
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
8,9
13,14 15,16 17,18
Sensing Input Range 3, Three-Phase-and-Neutral
Phase
2.25
3.00 4.50 5.25 6.75
7.50 9.00 9.75
11.25
12.00
8,9
13,14 15,16
—
Neutral
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
—
—
—
17,18
Sensing Input Range 4, Three-Phase-and-Neutral
Phase
0.75
1.00 1.50 1.75 2.25
2.50 3.00 3.25
3.75
4.00
8,9
13,14 15,16
—
Neutral
2.25
3.00 4.50 5.25 6.75
7.50 9.00 9.75
11.25
12.00
—
—
—
17,18
Sensing Input Range 5, Three-Phase-and-Neutral
Phase or
Neutral
2.25 3.00
4.50 5.25 6.75 7.50
9.00
9.75
11.25 12.00
8,9
13,14 15,16 17,18
Sensing Input Range 6, Three-Phase-and-Neutral
Phase or
Neutral
0.15 0.20
0.30 0.35 0.45 0.50
0.60
0.65
0.75
0.80
8,9
13,14 15,16 17,18
Sensing Input Range 7, Three-Phase-and-Neutral
Phase
0.45 0.60
0.90 1.05 1.35 1.50
1.80
1.95
2.25
2.40
8,9
13,14 15,16
—
Neutral
0.15 0.20
0.30 0.35 0.45 0.50
0.60
0.65
0.75
0.80
—
—
—
17,18
Sensing Input Range 8, Three-Phase-and-Neutral
Phase or
Neutral
0.45 0.60
0.90 1.05 1.35 1.50
1.80
1.95
2.25
2.40
8,9
13,14 15,16 17,18
Sensing Input Range 9 (All Other Sensing Types)
*
HIGH
0.45 0.60
0.90 1.05 1.35 1.50
1.80
1.95
2.25
2.40
Same as Range 1
LOW
0.15 0.20
0.30 0.35 0.45 0.50
0.60
0.65
0.75
0.80
Same as Range 1
* For relays with sensing input ranges 1 or 9, connect the system wiring to the current sensing terminals
for the desired range (HIGH or LOW).
BE1-51