BE1-50/51B-232 General Information

1-1

SECTION 1

GENERAL INFORMATION

INTRODUCTION

BE1-50/51B-232 protective relays are direct replacements for General Electric, IAC relays. BE1-50/51B-
232 protective relays are enclosed in an S1 case. The BE1-50/51B-232 has a 5 ampere current sensing
input. Compatible IAC model numbers are listed in Table 1-1.

Table 1-1. GE IAC Relays Suitable for Direct Replacement

IAC Model Number

Curve Type

12IAC51A

A

Inverse

12IAC51B

A

Inverse with Instantaneous

12IAC53A

A

Very Inverse

12IAC53B

A

Very Inverse with Instantaneous

12IAC55A

A

Short Time

12IAC55B

A

Short Time with Instantaneous

12IAC66A

A

Long Time

12IAC66B

A

Long Time with Instantaneous

12IAC77A

A

Extremely Inverse

12IAC77B

A

Extremely Inverse with Instantaneous

 Any digit covering all pickup ranges except 50 Hz models.

Basler Electric BE1-50/51B-232 protective relays are self-powered, microprocessor-based, non-
directional phase or ground relays that monitor the magnitude of a single-phase ac current to provide
accurate instantaneous and time overcurrent protection for 60 Hz power systems. Each model covers 15
popular time characteristics, a wide range of pickup settings, and field selectable instantaneous or
integrating reset.

FEATURES

A wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.

BE1-50/51B-232 overcurrent relays have the following standard features.

 Independent time and instantaneous elements
 A secure method to manually trip the breaker at the relay front panel
 Direct reading front panel controls
 Minimum pickup setting for safety during installation
 Time characteristics extend to a pickup multiple of 40
 Rugged draw-out construction with steel case
 Gravity latching targets retain indication without power
 Built-in accuracy eliminates internal adjustments
 Minimum transient overreach
 Field selectable characteristic curve selection similar to either GE IAC or ABB type curves
 Field selectable instantaneous or integrating reset
 Field selectable 0.0, 0.1, 0.2, or 0.3 second, fixed, instantaneous delay

Internal switches provide for selecting instantaneous element delays of 0.0, 0.1, 0.2, or 0.3 second,
characteristic curve group selection for either GE IAC or ABB type curves, and instantaneous or
integrating reset characteristics. Switch location and description is provided in Section 2.