Fireplace Placement Requirements
Minimum Framing Dimensions
A 1" clearance is required along the sides and back of the fireplace. The 1" stand-offs on the sides
and 6-3/8" stand-offs on the top of the fireplace are designed to separate the fireplace from the
framing members. These stand-offs may contact the framing members but no material may be placed
between the stand-offs.
54-3/4" Min.
44-1/4"
20-1/2"
46-3/4"
3" Clearance Min. Above Vent
The center of the vent is a
minimum 47-3/4" above the
base of the fireplace.
1" Clearance Min. to
the Sides of Vent
The fireplace enclosure
must not be less than
54-3/4" above the base
of the fireplace.
1" Clearance Min.
Below Vent
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Clearances
•
When installed, walls in front of the fireplace must be a minimum 6" to the side of the faceplate.
•
Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.
•
Fireplace must be placed so the vents below and above the glass do not become blocked