Floor Protection
When the stove is installed directly on carpeting, vinyl or other combustible material other than
wood flooring, the stove must be installed on a metal or wood protection panel extending the full
width and depth of the stove.
Vent Requirements
The vent must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1
and the requirements listed below. Furthermore, the vent must be installed to meet the
installation requirements of the vent manufacturer.
¥
Minimum 5' vertical rise from top of stove (see the illustration below)
¥
The horizontal run may not exceed 50% of the vertical rise
¥
Use 4" dia. B vent for entire system from one manufacturer (don't mix brands)
- or -
Use high temperature factory built chimney and connector with listed gas
chimney liner running the entire length
¥
The vent must not service another appliance
¥
1" clearance to all combustibles must be maintained
¥
Must meet all of the vent manufacturer's requirements
¥
Vent termination must be above the roof and not below any eaves or overhangs
Type B Vent
Vent must
terminate a
minimum 1'
above the roof.
Listed Gas
Chimney Liner
Maintain 1"
minimum
clearance
Provide a 1/4" rise
for every 12" run.
Min. 5' Rise
High
temperature
factory built
chimney and
connector
Chimney with Liner
Standard Installation
Exterior Vent
Min. 5' Rise
The total
horizontal
run must
not exceed
50% of the
vertical rise
Do not block gas
vent termination