26 Installation
(for qualified installers only)
© Travis Industries
4140922
100-01410
Facing Requirements
The included fiber board is required and must remain attached to the fireplace (see “a” below).
Non-combustible facing must extend 7-3/4” (197mm) above the face of the fireplace (see “c” below).
Drywall or other combustible may not be place on top of this non-combustible area.
Drywall (or other combustible) may be placed above the non-combustible facing (see “b” below) and
to the sides and below the fireplace face. This combustible facing must be a minimum 7-3/4”
(197mm) above the face of the fireplace (see “b” below).
Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but must
not extend over the glass/grill opening (see “d”). This area must remain open to allow for glass frame
removal and air flow.
(a) Fiber Board (included with fireplace)
(c) Tile (or other non-combustible)
(b) Drywall (or other combustible)
(d) Perimeter of Fireplace (may be covered)
c
b
b
c
a
b
b
d
a