beautypg.com

Electrical characteristics -4, Physical characteristics -4, Safety agency approval -4 – AMETEK SGWC Series User Manual

Page 14

background image

1-4

M550129-20 REV D

WARNING

The temperature of the inlet water must be above the dew
point to prevent internal condensation.

1.4.1.9 CHASSIS COOLANT CONNECTION

Chassis inlet and outlet: 3/8

” FNPT brass bulkhead fittings, double-D with 1.25” outer diameter

and 1.125” across flats


Quick-Disconnect Option:
Chassis adapter fitting: Swagelok # B-6-AT-6
Chassis quick-disconnect plug: SMC # KKA4P-03M
Mating quick-disconnect socket: SMC # KKA4S-03M

1.4.2 ELECTRICAL CHARACTERISTICS

1.4.2.1 AC INPUT POWER FACTOR

0.95%, typical, at full-rated load and nominal AC input voltage

1.4.2.2 AC INPUT CURRENT

32AAC, maximum, at 342VAC input, full-rated load, 87% efficiency, 0.95 power factor

1.4.3 PHYSICAL CHARACTERISTICS

1.4.3.1 DIMENSIONS

EIA-310 3U chassis size:

Width: 19.00 in (48.3 cm), front panel

Depth: 25.95 in (65.9 cm), rear of front panel to rear panel, with additional protrusion from rear
panel of 1.48 in (3.76 cm) to output busbars and 2.50 in to plastic busbar cover
Height: 5.22 in (13.3 cm), front panel

1.4.3.2 WEIGHT

10kW unit: 85 lb ( 38.6 kg); 15kW unit: 97 lb (44.0 kg)

1.4.4 SAFETY AGENCY APPROVAL

This product has been designed and manufactured to industry standards that ensure
appropriate levels of protection for operator safety. It is designed to meet the requirements of
the CE Mark as specified per safety standard EN 61010-1.

This page intentionally left blank.