ET / ET60 - Electric Tilt Mechanism
Operation Details
AC1
Gives an output of 240V
(or 110V).
AC2
Outputs stay live for 120
seconds after the OUT or
IN functions are selected.
EMERGENCY STOP
This connection will stop all
functions of the mechanism once
broken / removed. This is where we
recommend wiring a safety device -
For a range of safety devices see
control, safety & accessories section
in product brochure.
SLQV
RS232
- Use an RJ25 connector
in the socket marked
RS232 on the control box
to operate using RS232
Details
Baud rate: 9600
Stop bit:
1
Parity:
None
Databits:
8
Pin 1: RX
Pin 6 : TX
Pin 3 & 4: GROUND
Pin 2: TX
Pin 3: RX
Pin 5: GROUND
IMPORTANT
Ensure protocol is entered exactly
as written, including Carriage Return
(Enter / ASCII 13).
RJ25
9 PIN D
PIN 1: RX
TO
PIN 2: TX
PIN 6: TX
TO
PIN 3: RX
PIN 3: GROUND
TO
PIN 5: GROUND
PIN 4: GROUND
TO
PIN 5: GROUND
Protocol
Action
fa_in Carriage Return (Enter )
Device IN
fa_out Carriage Return (Enter )
Device OUT
fa_stop Carriage Return (Enter )
Device STOP (At any position)