Analog outputs interface pea208, Overview, Connections – CUE Power Express User Manual
Page 12: Pe bus
![background image](https://www.manualsdir.com/files/768529/content/doc012.png)
3.6. Analog Outputs Interface PEA208 .................................................
3.6.1. Overview
PEA208 is a two-channel analog output 0 - 10V interface
for devices with analog control 0 - 10V (dimmable ballast
for fluorescent lamps – Osram, Siemens, Helvar, Philips,
dimmers, frequency converters ...). Analog outputs have
10–bit resolution (1024 levels). Sink current can be up to
100mA to each output (more then 100 of ballasts). Unit
has two switching outputs (max. 8A) automatically
switched on, if analog output voltage is greater then 1V
(for power supply of ballasts). The unit features PEbus and
contact closure control. Programmable parameters (inputs
response, min. and max. value of output voltage, scan
speed). Indication of output levels by yellow OUT LEDs.
Indication of power by green P/D LED. This LED is
flashing while data is being transmitted or received
through
power by green P/D LED. This LED is
flashing while data is being transmitted or received
through the PEbus.
the PEbus.
3.6.2. Connections
3.6.2. Connections
LOAD
max. 8 A
DOW
N
1
UP1
GND
DOW
N
2
UP2
GND
PEbus
PW
R O
UT1
PW
R O
UT2
N
E
UT
RA
L
N
E
UT
RA
L
LIVE
LIVE
OU
T1+
OUT
1
-
OU
T2+
OUT
2
-
N
L
N
L
A+
A-
DIMMABLE BALLAST
1-10 V ANALOG CONTROL
N
L
A+
A-
DIMMABLE BALLAST
1-10 V ANALOG CONTROL
max.
100 ballasts
User Manual Power Express
www.cue.cz