Ratings & type descriptions – Crompton Controls CIMR-JC4A0001BAA User Manual
Page 7
7
ratings & type Descriptions
Inverter Series
Version
J1000
J
1st
A
Specification
Coating Specification and Protection
Japanese spec.
A
Standard
A
European spec.
C
Moisture (humidity)/Dust-proof
M
USA spec.
U
Oil-proof
N
Vibration-proof
S
Input Voltage
Single-phase 230 VAC
B
Type
Three-phase 200 VAC
2
Fin
Filter
Protection level
Three-phase 400 VAC
4
Standard
No
IP20 without top cover
B
Standard
No
NEMA1(IP20)
F
Customer Specification
Standard
A
CIMR-
J
C
B
A
0001
B
A
A
Voltage class
400 V
Inverter
Model
Three Phase Inverter CIMR-JC4A
0001
0002
0004
0005
0007
0009
0011
Inverter
output
Motor output kW at normal duty *
1
0.4
0.75
1.5
2.2
3.0
3.7
5.5
Motor output kW at heavy duty *
1
0.2
0.4
0.75
1.5
2.2
3.0
3.7
rated output current at normal duty*
2
[A]
1.2
2.1
4.1
5.4
6.9
8.8
11.1
rated output current at heavy duty*
3
[A]
1.2
1.8
3.4
4.8
5.5
7.2
9.2
Overload
120% for 60 sec at normal duty, 150% for 60 sec at heavy duty
from inverter rated output current
Rated output power*
4
at normal duty*
2
[kVA]
0.9
1.6
3.1
4.1
5.3
6.7
8.5
Rated output power*
4
at heavy duty*
3
[kVA]
0.9
1.4
2.6
3.7
4.2
5.5
7.0
Max. output voltage
Three-phase 380 to 480 V (proportional to input voltage)
Max. output frequency
400 Hz
Inverter
input
Rated input voltage
Three-phase 380 to 480 V +10%/-15%
Rated input frequency
50/60 Hz +/-5%
*
1
The motor capacity (kW) refers to a YASKAWA 4-pole, 60 Hz, 400 V motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current.
*
2
This value assumes a carrier frequency of 2 kHz to Swing PWM. Increasing the carrier frequency requires a reduction in current.
*
3
This value assumes a carrier frequency of 8 kHz. Increasing the carrier frequency requires a reduction in current.
*
4
Rated output capacity is calculated with a rated output voltage of 440 V.
*
1
Drives with a single-phase power supply input have three-phase output. Single-phase motors cannot be used.
*
2
The motor capacity (kW) refers to a YASKAWA 4-pole, 60 Hz, 200 V motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current.
*
3
This value assumes a carrier frequency of 2 kHz to Swing PWM. Increasing the carrier frequency requires a reduction in current.
*
4
Rated output capacity is calculated with a rated output voltage of 220 V.
*
5
This value assumes a carrier frequency of 10 kHz. Increasing the carrier frequency requires a reduction in current.
*
6
This value assumes a carrier frequency of 8 kHz. Increasing the carrier frequency requires a reduction in current.
Voltage class
200 V
Inverter
Model
Three Phase Inverter CIMR-JC2A
0001
0002
0004
0006
0010
0012
0020
Single Phase*
1
Inverter CIMR-JCBA
0001
0002
0003
0006
0010
–
–
Inverter output
Motor output kW at normal duty*
2
0.2
0.4
0.75
1.1
2.2
3.0
5.5
Motor output kW at heavy duty *
2
0.1
0.2
0.4
0.75
1.5
2.2
4.0
Rated output current at normal duty [A]*
3
1.2
1.9
3.5 (3.3)
6.0
9.6
12.0
19.6
Rated output current at heavy duty [A]
0.8*
5
1.6*
5
3*
5
5.0*
5
8.0*
6
11.0*
6
17.5*
6
Overload
120% for 60 sec at normal duty, 150% for 60 sec at heavy duty
from inverter rated output current
Rated output power*
4
at normal duty [kVA]*
3
0.5
0.7
1.3
2.3
3.7
4.6
7.5
Rated output power*
4
at heavy duty [kVA]
0.3
0.6
1.1
1.9
3.0
4.2
6.7
Max. output voltage
Three-phase power supply: three-phase 200 to 240 V (relative to input voltage)
Single-phase power supply: three-phase 200 to 240 V (relative to input voltage)
Max. output frequency
400 Hz
Inverter
input
Rated input voltage
Three-phase 200 to 240 V +10%/-15% , Single-phase 200 to 240 V +10%/-15%
Rated input frequency
50/60 Hz, ±5%