Specifications – Crompton Controls CIMR-JC4A0001BAA User Manual

Page 4

background image

4

YASKAWA J1000

Specifications

Specifications

Control Characteristics

Control methods

V/f Control

Frequency Control Range

0.01 to 400 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max. output frequency (−10°C to +50°C)
Analog input: within ±0.5% of the max. output frequency (25°C ±10°C)

Frequency Setting

Resolution

Digital input: 0.01 Hz
Analog input: 1/1000 of max. frequency

Output Frequency Resolution

1/2

20

x Maximum output frequency (E1–04)

Frequency Setting Signal

Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)

Starting Torque

150% / 3 Hz

Speed Control Range

1:20

Accel/Decel Time

0.0 to 6000.0 s (4 selectable settings of independent acceleration and deceleration time)

Braking Torque

q

Short-time decel torque*

1

: over 150% for 0.1/0.2 kW motors, over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors,

and over 20% for 2.2 kW and above motors.

w

Continuous regen. torque: approx. 20% (approx. 125% with dynamic braking resistor option*

2

: 10% ED, 10 s, internal braking

transistor)

V/f Characteristics

User-set programmable V/f preset patterns possible

Main Control

Functions

Momentary power loss ride-thru, Speed search, Multi-Step Speed (max. 9 steps), Accel/decel time switch, S-curve accel/decel, 3-wire

sequence, Cooling fan on/off, Slip compensation, Torque compensation, Frequency jump, Upper/lower limits for frequency reference,

DC injection braking at start and stop, Overexcitation braking, Fault restart ...

Protection Function

Motor Protection

Motor overheat protection based on output current

Momentary Overcurrent Protection

Drive stops when output current exceeds 200% of Heavy Duty Rating

Overload Protection

Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)*

3

Overvoltage Protection

200 V class: Stops when DC bus exceeds approx. 410 V

400 V class: Stops when DC bus exceeds approx. 820 V

Undervoltage Protection

Stops when DC bus voltage falls below the following levels:

190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350 V (3-phase 380 V)

Momentary Power Loss Ride-Thru

Stops after approx. 15 ms (default).

Heatsink Overheat Protection

Protected by thermistor

Braking Resistance Overheat

Protection

Overheat input signal for braking resistor (optional ERF-type, 3% ED)

Stall Prevention

Separate settings allowed during acceleration and during run. Enable/disable only during deceleration.

Ground Fault Protection

Protected by electronic circuit*

4

Charge LED

Charge LED remains lit until DC bus falls below approx. 50 V

Operating Environment

Area of Use

Indoors

Ambient Temperature

-10 to +50°C (IP20 open chassis), -10 to +40°C (NEMA Type 1)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20 to +60°C (short-term temperature during transportation)

Altitude

Max. 1000 m (output derating of 1% per 100 m above 1000 m, max. 3000 m)

Shock

10 to 20 Hz (9.8 m/s

2

) max., 20 to 55 Hz (5.9 m/s

2

) max.

Safety Standard

UL508C

Protection Design

IP20 open-chassis, NEMA Type 1 enclosure (option)

*

1

Momentary average deceleration torque refers to the torque required to decelerate the motor (uncoupled to the load) from the rated motor speed down to zero in the shortest time.

*

2

Parameter L3-04 should be disabled when a Braking Resistor or Braking Resistor Unit is connected.

*

3

Overload protection may be triggered at lower levels if output frequency is below 6 Hz.

*

4

Protection may not be provided under the following conditions as the motor windings are grounded internally during run:

• Low resistance to ground from the motor cable or terminal block.
• Drive already has a short-circuit when the power is turned on.