Introduction, Presentation – ABUS Technologies PT-FD Series Pressure Transmitter User Manual

Page 4

background image

ABUS TECHNOLOGIES INC.

4


PT-FD

1. INTRODUCTION


The PT-FD series of transmitters features, a flush diaphragm process connection.

They are specifically designed for the measurement of viscous fluids or media containing

solids that may clog a process connection. Flush diaphragm pressure transmitters are

available in pressure ranges as low as 1500INWC.

The flush diaphragm could be easily flushed or cleaned to remove dirt. The model

offers reliable and accurate pressure measurement of the gases, viscous liquids and

slurries. And for the electrical parts adopt high performance chips, and deal with special

amplified chip, integrated configuration, and smart profile.

A wide range of electrical

connection and process connection options are available to meet almost any requirement.

2. PRESENTATION


2.1 Features

1. Improved media compatibility.

2. Excellent resistance to corrosive processes.

3. Compact Design and Rugged construction.

4. Wide range of available process connections and signal outputs.

5. OEM process to fit application of the customers.

6.

Resistant to pressure spikes and vibrations.

7. Stainless steel case and wetted parts

8. Can be assembled to diaphragm seals for special applications.


2.2 Technical Parameters

Accuracy:

±0.25%FS (BFSL)

±0.5%FS (limit point calibration)

Ranges:

-1 bar… 0 bar…600 bar

Output:

0...5 V, 0...10 V, 0...20 mA, 4...20 mA

Power Supply:

24Vdc (10~36Vdc)

Maximum Pressure:

1.5 x F.S.

Adjustability Zero / Span:

± 10 using potentiometers inside the instrument

Electrical Connections:

M12 connector, five Pin bendix connector, Hirschman and Direct

down-lead.

Operating temperature:

-40 ~ 125

°C (higher range, on request.)

Ambient temperature:

-20 ~ +80°C

Process Connection:

G1/4, M20 x 1.5, 1/4NPT (Customized On request)