7.2 Key Operation Instruction

The instrument will automatically enter PV/SV display block 3.5s after applying

power. The PV screen and the SV screen will display process value and set value

respectively.

Parameter setting block: Under PV/SV display block, the instrument will enter

parameter setting block by pressing down SET key for 2s. The PV screen displays

parameter name and the SV screen displays parameter value, the last figure of which

will flash. Edit parameter value with ◄, ▼, ▲ keys. Then press SET key to confirm the

change and switch to the next parameter name, or press down SET key for 2s to

confirm the change and return to PV/SV display block. The instrument will return to

PV/SV display block if there is no key action for 60s, in this case, the last change to

the parameter will be cancelled.

Self-tuning block (only available when LOC=0 and the instrument are under PID

control mode): Under PV/SV display block, the instrument will enter self-tuning block

by pressing down key for 2s. The PV screen displays the process value, and the SV

screen displays a flashing -At- at interval of 0.5s (during the process, the instrument

can enter and exit parameter setting block and output display block with no effect on

self-tuning. But the self-tuning prompt will disappear). On completion of self-tuning, the

PID parameters of the instrument will be automatically changed and saved and the

instrument will return to PV/SV display block automatically. Press down ▼ key for 2s

when -At- on the SV screen stops flashing to exit the self-tuning block during self-

tuning process.

8. MAINTENANCE

Metrological verification should be conducted annually for the instrument. If the

instrument goes beyond error limit, which often results from a damper environment,

dust or corrosive gas, the inner part of the instrument should be cleaned and dried. In

case the accuracy can not be restored by cleaning and drying, the instrument should

be sent back as default product to the factory for troubleshooting.