beautypg.com

Introduction, Presentation – ABUS Technologies UC Series Universal Process Controller User Manual

Page 4

background image

ABUS TECHNOLOGIES INC.

4



UC

1. INTRODUCTION

UC508 economy is a Microprocessor based Digital Process Controller, which

can be applied in high-precision measurement and control of temperature, pressure,
discharge, liquid level and humidity etc... A four-digit LCD dual display shows
measured value and set-value for all programming parameters. Instrument
configuration is achieved from the front panel keyboard, without any hardware change.
The user should read this manual thoroughly before using the instrument. It must be
handled with care and should be used accordingly for best results.

2. PRESENTATION



2.1 Features

1. Input signal: Thermocouple, RTD, direct voltage, current programmed from the front panel.
2. Outputs can be set on-off control or PID control with configurable direct/reverse action modes.
3. The input uses digital correction system; there is nonlinear correction form of communal used

thermocouple and resistance thermometer detector.

4. Control output modes hold out relay contact switch, solid-state relay driving voltage, and single-

phase thyristor zero-crossing trigger signal etc.

5. Comprehensive self-detection and protection. In case of error, it provides automatic repair or

prompt message and closes the output.


2.2 Technical Parameters

Input Signals:

Refer to table 6.1 Input Signal

Intrinsic error:

± 0.5% FS ± 1 digit

Sampling period:

<0.3s

Working power supply:

220V 10%/50~60Hz, power consumption<5W.


Control modes
(freely changeable with keypad):

On-off control (configurable direct/reverse action and differential gap)

PID control (configurable direct/reverse action, manual or automatic of PID parameters)

Alarm modes (freely changeable with keypad):

One way of programmable alarm output is provided with a number of alarm modes including
higher limit, lower limit (Relay output).

In addition, the alarm feature can also be temporarily disabled when applying the power.

Output specifications:

Output module of relay contact switch: Normally open (absorbed by varistor), 30VDC/2A,
240VAC/2A.

Output module of solid-state relay (SSR) driving voltage: 12VDC/25mA.

Output module of single-phase thyristor zero-crossing trigger signal: 100~380VAC/50~60Hz,
capable of triggering

5-500A TRIAC or 2 SCRs in inverse parallel connection or thyristor power module.

Operating Environment:

Recommended Temperature: 0~50
Relative Humidity: