ABUS Technologies LPI-PT Loop Powered Indicator User Manual

Page 9

background image

ABUS TECHNOLOGIES INC.

9



LPI-PT

 “A” or “B” to change the setting either “on” or “off”. “on” means the parameter

followed is valid, and the Alarm was expressed by the twinkle of the last decimal

point. And “off” means to cancel the alarm function.

 “A+B” to confirm and store setting and return to the menu item.

7. First alarm point

Press button “A”, unit is displayed. It is configured in percentage of span.

8. Second alarm point

Press button “A”, unit is displayed. The method of setting is the same as

step 7.

9. The direction of first alarm point

Press button “A”, unit is displayed.

 “A+B” menu item for setting.

 “A” or “B” to change the setting either “up” or “down”. “up” means alarm while

the value change from small to big, and “down” means alarm while the value

change from big to small.

 “A+B” to confirm and store setting and return to the menu item.

10. The direction of second alarm point

Press button “B”, unit is displayed. Other is the same as step 9.

11. The Delay

Press button “B”, unit is displayed.

 “A” menu item for setting.

 “A” to increase it by step 0.5s and “B” to reduce it by step 0.5s. (Min=0s,

Max=30s step 0.5)

 “A+B” to confirm and store setting and return to the menu item.

 “A” returns to the original interface. And all setting is completed.