ABUS Technologies LPI-PT Loop Powered Indicator User Manual
Page 9

ABUS TECHNOLOGIES INC.
9
LPI-PT
“A” or “B” to change the setting either “on” or “off”. “on” means the parameter
followed is valid, and the Alarm was expressed by the twinkle of the last decimal
point. And “off” means to cancel the alarm function.
“A+B” to confirm and store setting and return to the menu item.
7. First alarm point
Press button “A”, unit is displayed. It is configured in percentage of span.
8. Second alarm point
Press button “A”, unit is displayed. The method of setting is the same as
step 7.
9. The direction of first alarm point
Press button “A”, unit is displayed.
“A+B” menu item for setting.
“A” or “B” to change the setting either “up” or “down”. “up” means alarm while
the value change from small to big, and “down” means alarm while the value
change from big to small.
“A+B” to confirm and store setting and return to the menu item.
10. The direction of second alarm point
Press button “B”, unit is displayed. Other is the same as step 9.
11. The Delay
Press button “B”, unit is displayed.
“A” menu item for setting.
“A” to increase it by step 0.5s and “B” to reduce it by step 0.5s. (Min=0s,
Max=30s step 0.5)
“A+B” to confirm and store setting and return to the menu item.
“A” returns to the original interface. And all setting is completed.