Operating parameters, Nskw installation manual, Heating mode – WaterFurnace Envision Hydronic User Manual
Page 38: Cooling mode
38
NSKW INSTALLATION MANUAL
Operating Parameters
Heating Mode
Entering
Load Temp (°C)
Entering
Source Temp (°C)
Suction
Pressure (kPa)
Discharge
Pressure (kPa)
Superheat
(°C)
Subcooling
(°C)
15
-15
358-462
1344-1565
4-9
3-8
0
462-565
1434-1620
4-8
3-8
10
655-779
1489-1689
4-8
3-7
20
855-993
1551-1758
4-11
3-8
30
986-1151
1586-1896
8-14
4-7
25
-15
372-476
1951-2179
4-9
4-8
0
476-579
2020-2227
6-7
4-10
10
676-862
2082-2310
7-8
4-9
20
834-1020
2144-2386
8-10
4-9
30
993-1234
2199-2503
8-14
4-9
35
-15
386-490
2544-2792
4-6
3-8
0
531-586
2606-2834
6-7
4-8
10
441-869
2675-2930
7-8
4-8
20
848-359
2744-3020
8-10
2-7
30
1020-1317
2813-3116
8-12
2-7
50
-15
407-510
3137-3413
4-10
2-9
0
510-600
3199-3447
3-9
3-9
10
731-883
3268-3551
3-9
3-8
20
862-1076
3344-3654
3-9
2-8
30
operation not recommended
9/26/11
Cooling Mode
Entering
Load Temp (°C)
Entering
Source Temp (°C)
Suction
Pressure (kPa)
Discharge
Pressure (kPa)
Superheat
(°C)
Subcooling
(°C)
10
0
593-683
931-1103
7-12
1-8
10
634-738
1317-1475
6-11
2-8
20
676-793
1710-1848
3-8
3-9
30
696-820
2310-2530
3-8
4-9
45
724-841
2930-3206
4-9
6-11
20
0
614-731
903-1124
8-11
2-3
10
710-862
1338-1538
6-8
3-5
20
814-986
1772-1882
6-8
5-7
30
862-1041
2372-2627
4-7
7-8
30
0
634-779
883-1145
8-11
2-3
10
793-986
1358-1606
6-8
3-5
20
889-1089
1834-2027
6-8
5-7
30
1034-1158
2441-2723
4-7
7-8
45
0
662-834
862-1172
31-36
1-11
10
876-1110
1379-1675
23-29
2-4
20
1089-1379
1896-2172
12-21
4-11
30
operation not recommended
NOTE: Operating parameters based on normal conditions with 0.19 L/s per kW output for the load and source.