beautypg.com

Envision console controls cont – WaterFurnace Envisio Series Console User Manual

Page 36

background image

36

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls cont.

Maintenance

MinClgSetpt 60.0

ºF

MaxHtgSetpt 89.9 ºF

W Coil LoLim1 30.0 ºF

W Coil LoLim2 15.0 ºF

TmpOccTime 120 min

Rev Vlv Default Heating

BO5 Mode Network

CompStrtDly 90 sec

SpaceT Offset -1 ºF

DehumEnaDis Dis

Acc1 Action On Comp

Acc2 Action On Fan

SW1 OFF

SW2 OFF

SW3 ON

SW4 OFF

SW5 OFF

SW6 OFF

SW7 ON

SW8 OFF

SW9 OFF

SW10 ON

SW11 OFF

SW12 OFF

ECM

ALARM SUMMARY

^/High Pressure

Alarms

Press right arrow key

one time from

Maintenance Menu

No more than three

speeds should be “ON”

at one time

Alarm #Events

Condensate 0

Hi Pressure

0

Low Pressure

0

Low Temp

0

Bad Sensor

0

Alm-History

NOTE: This FX10 application implements an alarm history which is reset
only by cycling power . This history shows on the Alm-History page. Any

alarm showing 4+ events has occurred more than 4 times.

Alarm lock-outs are reset by cycling power, by pressing the “ESC” and

Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.

Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously

for a minimum of 15 seconds and releasing. Test mode times out after 30

minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing . Test Mode bypasses the On Delay (90 sec)

and Random Start timers for quicker troubleshooting. It also allows cycling

the reversing valve without compressor shutdown.

MUI Menu Navigation for Single Compressor - Envision Water-to-Air