beautypg.com

Wiring schematics cont, Led display mode table – WaterFurnace Envisio Series Console User Manual

Page 24

background image

24

ENVISION CONSOLE INSTALLATION MANUAL

Operational Logic Table

Mode

Htg

Clg

Inputs

Fan

Comp

RV

Y

Y,O

Fan

G

ON

ON

ON

OFF

ON

ON

OFF

ON

OFF

SW1 - #4 On, SW2 Off
Drain pan overflow lockout

FS thermistor (loop <15°F, well < 30°F) lockout
High pressure >600 PSI lockout
Low pressure < 40 PSI lockout
Not used
Microprocessor malfunction*
Not Used

SW2 status (Off = down position, On = up position)

Drain

Water Flow

High Press

Low Press
Air Flow

Status
DHW Limit
HWD

LED

Normal Display Mode

SW1- #4 On, SW2 On

Drain pan overflow
FS thermistor (loop <15°F, well <30°F)
High pressure > 600 PSI
Low pressure < 40 PSI
Not used
Not used
Not used
SW2 in the On position

Current Fault Status

SW1- #4 Off, SW2 Off

Y
G
O

ES
NS
LS

Not Used

Off position

Inputs

Compressor

FAN

O

ES
NS

LS

Not Used

On position

Outputs

Diagnostic Modes

SW1- # 4 Off, SW2 On

Drain

Water Flow
High Press
Low Press

Air Flow

Status

DHW Limit
HWD

LED

LED Display Mode Table

CC Relay

Fan Relay

CC

CCG

C
C

R
R

FAN

FANCOM

R

C

Y

O

G

LO

ES

NS

LS

P3

P1

SW1

Microprocessor

Logic Control

17P529A01

P2

6

1

7

2

8

3

9

4

10

5

Versatec Logic Board Physical Layout

Switch

OFF

ON

SW1 - 1

SW1 - 2

SW1 - 3

SW1 - 4

SW1 - 5

SW2

Test - Selected timings sped up to facilitate
troubleshooting

Loop - Closed loop freeze sensing setting (15°F)

IO Display * - Enables Input/Output display on external
LED board*

Enables NS features

Motorized Valve - 1.5 minute compressor on delay

OFF * - Normal or Input display mode activated

ON * - Current fault or Output display
mode activated

Normal - Standard timings

Well - Open loop freeze sensing setting (30°F)

Normal * - Unit status display

Normal - Standard thermostat operation

Normal - Standard delay on call from
compressor used

*Refer to LED Display Mode table for position of SW1-4 and SW2

Logic Board DIP Switch Settings

Normal Control Timing Table

Blower off delay

Compressor on delay

Short cycle delay

Minimum compressor on time

High pressure fault recognition delay

Low pressure fault recognition delay

Condensate overflow fault recognition delay

Low pressure fault bypass delay

Freeze sensing fault bypass delay

Motorized valve delay

Random start delay

Freeze sensing fault recognition delay

30 seconds

10 seconds

5 minutes

60 seconds (except for fault condition )

Less than 1 second

30 seconds

30 seconds

30 seconds

2 minutes

2 minutes

90 seconds

0 - 25 seconds

Test Control Timing Table

Blower off delay

Compressor on delay

Short cycle delay

Minimum compressor on time

High pressure fault recognition delay

Low pressure fault recognition delay

Condensate overflow fault recognition delay

Low pressure fault bypass delay

Freeze sensing fault bypass delay

Motorized valve delay

Random start delay

Freeze sensing fault recognition delay

5 seconds

2 seconds

15 seconds

5 seconds (except for fault condition )

Less than 1 second

30 seconds

30 seconds

30 seconds

0 seconds

0 seconds

90 seconds

0 seconds

*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a
microprocessor malfunction.

Wiring Schematics cont.

208-230-265/60/1

VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT

Legend for Schematic [A]