When using an extension cord, the cord should be

2

a minimum of 1.5 mm (15 awg) and no longer than
7.5 m. Otherwise Voltage may drop and damage
the compressor! The cable must be completely
unrolled.

English Instruction Manual ENVIRO

Be sure the power is off before examining or
repairing the recovery unit. Risk of serious in-
jury and death!

Use only authorized refillable refrigerant tanks.
The Unit requires the use of recovery tanks with
a minimum working pressure of 40 bar (580psi).
Do not overfill the recovery tank. Tank is full at
80% capacity. There should be enough space
for liquid expansion.
Overfilling of the tank may cause a violent explo-
sion.

A Charging scale is required to prevent overfilling.

It is compulsory to wear safety goggles, and pro-
tective gloves while working with refrigerants to
protect skin and eyes from refrigerant gas and liq-
uid. Avoid any contact with caustic gas or liquid.
Risk of serious injury!

Be sure that any room where work is being con-
ducted is thoroughly ventilated.