OPTI-UPS DS3000B-RM User Manual
Page 15
21
UPS configurations
1. Various settings that have been chosen are shown in the UPS setting display.
2. To enter configuration mode, press the “FUNC” button for one second. The first
configuration parameter will be shown on the LCD display.
3. Press the “FUNC” button to scroll through the parameters.
4. Press the “ENTER” button to select the parameter.
5. Press the “FUNC” button to scroll through the options for the selected parameter; Press
the “ENTER” button to select the option.
You may be prompted to save the selection, if so press the “ENTER” button to either
confirm or save your selection. Other options are saved and started automatically. See
the table below for further details.
6. If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the
configuration mode and return to normal mode displaying Line mode.
Caution!
The factory default settings do not necessarily have to be changed, although
you are free to tailor the UPS to your specific needs.
22
Settings
LCD
display
Explanation Selection
Factory
default
208/220/230/240 V
230V
Output Volt. Setting
O/P V
Setting
Select Nominal Voltage
100/110/115/120/127 V
120V
Input/Frequency I/P
F
Setting
Select input frequency
range when UPS goes into
free run mode
±2%
±5%
±7%
±5%
Input/Bypass
Voltage
I/P Bypass
Set
Select Input Voltage range
when bypass is available
±10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
Free Run
Set
Select if UPS can run in
Free run mode
(unsynchronized)
ON/OFF ON
Bypass
Enable/Disable at
Free run mode
Bypass
disable
If Enable is chosen, the
UPS can go to bypass when
unsynchronized.
Disable/Enable Disable
HE mode Setting
HE Mode
Set
Select if UPS runs in high
efficiency mode
ON/OFF OFF
Force Manual
Bypass
Manual
bypass
Permanently force UPS to
bypass. For service only.**
ON/OFF
OFF
Management of
Load groups
Outlet
Setting
You can put the two load
groups on and off form
front panel
1 ON & 2 ON
1 OFF & 2 ON
1OFF & 2 OFF
1 ON & 2 OFF
Both load
segments
ON
Do Battery Test
Battery Test
Detect battery is normal or
not.
Silence Function
Silence Set
Enable or disable silence
function
ON/OFF
OFF
Number of
External battery
Packs
Bat Cabinet
Set
This setting is needed
For UPS to predict
Backup time
0 (only internal batteries)
1(one external cabinet)
2 (two external cabinets)
0
Site wiring alarm
Sit Fault Set
You can enable or disable
the site wiring alarm
Enable /Disable
Disable
Select Language
Language
Select load language
English, German, French,
Spanish, Italian.
English
Set Generator Mode Generator
Set unit in generator mode.
***
ON/OFF OFF
Set RS232
communication
RS232
Control
Set RS232 communication
enable or disable
Enable/Disable Enable