OPTI-UPS TS1000B User Manual

Page 2

background image



Specifications

Model

TS 400

TS 500(B)

TS 650(B)

TS 1000(B)

Maximum Capacity

240W

300W

360W

480W

Topology

Line-interactive

On-battery Output Waveform

Simulated Sine Wave

Input Voltage Range

110/120V or 220/230/240V +/- 25%

Input Frequency

50Hz/60Hz Auto Sensing

Output Voltage Regulation

Rated voltage +/- 5%

Communication

RS232

*)

or USB

*)

Data Line Surge Protection

RJ11/RJ45

*)

Surge Energy Rating

480 Joules

Recharge Time to 90%

< 4 hours

Operating Temperature

0~40°C / 32~104℉

Storage Temperature

-20~60°C / -4~140℉

Relative Humidity

0 to 95% maximum, non-condensing

Audible Noise

<40 dBA

Unit Dimensions (L×W×H), mm

260Ч97Ч135

320Ч97Ч135

Net Weight, kg

4.2

6.0 (6.3)

6.2 (6.5)

6.3 (6.7)

EMC/RFI Compatibility

CE

Safety Certifications

CE, UL, cUL

*)

TS-B models only

Warranty


LIMITED WARRANTY
What the warranty covers:

We guarantee this product to be free from defects in material and
workmanship during the warranty period. If a product proves to be defective
in material or workmanship during the warranty period, we will at our sole
option, repair or replace the product with a like product.

How long the warranty is effective:

For accurate warranty period and conditions, please contact the local branch
offices or your dealers.

Who the warranty protects:

This warranty is valid only for the first consumer purchaser.

What the warranty does not cover:

1. Any product on which the serial number has been defaced, modified

or removed.

2. Damage, deterioration or malfunction resulting from:

a) Accident, misuse, neglect, fire, water, or other acts of nature,

unauthorized product modification, or failure to follow
instructions supplied with the product.

b) Repair or attempted repair by anyone not authorized by

OPTI-UPS.

c) The fault is the result of accidental damage or damage in transit

or transportation, including but not limited to liquid spillage.

d) Removal or installation of the product.
e) Causes external to the product.
f) Use of supplies or parts not meeting our specifications.
g) Normal wear and tear.
h) Any other cause which does not relate to a product defect.

3.

Removal, installation and set-up service charges.

Limitation of implied warranties:
There are no warranties, expressed or implied, which extend beyond the
description contained herein including the implied warranty of merchantability
and fitness for a particular purpose.
Exclusion of damages:
Our liability is limited to the cost of repair or replacement of the product. We
shall not be liable for:

1. Damage to other property caused by any defects in the product,

damages based upon inconvenience, loss of use of the product, loss
of time, loss of profits, loss of business opportunity, loss of goodwill,
loss of data, loss of software, costs of substitute equipment,
interference with business relationships, claims by third parties, or
other commercial loss, even if advised of the possibility of such
damages.

2. Any other damages, whether incidental, consequential or otherwise.
3. Any claim against the customer by any other party.

Troubleshooting

Problems

Possible Cause

Solution

UPS can’t turn on,
LED does not light

Power switch not pressed
long enough

Press the power switch for more than 1 second
until the UPS turns on

Battery voltage is less
than 10V

Recharge the battery for 6 hours by leaving the
UPS plugged in and the load disconnected from
the UPS.

Load is less than 20W at
battery mode

Disable “No Load Shutdown Function”

PCB failure

Call for service

UPS always at battery
mode

Input power cord is loose

Plug in the power cord firmly

Busted input fuse

Replace the fuse

Input voltage too high or

too low

Check input voltage

PCB failure

Call for service

Back up time too short

Battery is not fully

charged or defective

Recharge the battery for 6 hours. If the problem

is still present, replace the battery.

PCB failure

Call for service

Buzzer continuously

beeping

Overload

Remove some loads

Contact Information

OPTI-UPS USA:
Tel: +1-909-869-5700
Fax: +1-909-869-5730
[email protected]
www.opti-ups.com

OPTI-UPS Australia & New Zealand:
Tel: +64-9-441-6470
Fax: +64-9-441-6490
[email protected]
www.opti-ups.com

OPTI-UPS Europe:
Tel: +31-40-401-50-00
Tel: +31-40-262-80-57
Fax: +31-40-254-60-06
[email protected]
www.opti-ups.com

OPTI-UPS Germany:
Tel: +49-2173-9377670
Tel: +49-2173-9377671
Fax: +49-2173-9377672
[email protected]
www.opti-ups.com

OPTI-UPS Middle East:
Tel: +9714-8819-838
Fax: +9714-8819-938
[email protected]
www.opti-ups.com

OPTI-UPS Japan:
Tel: +81-3-3629-5782
Fax: +81-3-5682-0652
[email protected]
www.opti-ups.com

OPTI-UPS Asia:
Tel: +886-2-2246-7272
Fax: +886-2-2246-7312
[email protected]
www.opti-ups.com

Battery replacement procedure

Note: Follow this procedure for safe replacement of the battery. However,
small sparks may occur during the process. This is normal.

1. Turn off the UPS
2. Remove all plugs
3. Remove the four screws from the side slots
4. Gently remove the top cover
5. Disconnect the two wires connecting the battery to the UPS and pull

out the battery

6. Push the new battery into place
7. Connect the wires to the new battery, making sure that the red wire is

connected to the red battery terminal and the black wire to the black
battery terminal

8. Mount the cover and replace the screws
9. Follow the UPS turn on procedure