4. OPERATING GUIDE - DISCHARGING
4.7.2 NICKEL-CADMIUM BATTERY
Check each cell with a digital voltmeter near the end of the test.
A. If no cells have dropped below 1.0 volts at the end of the specified time the
battery has successfully completed the capacity test.
B. If any cells have dropped below 1.0 volt before or at the end of the capacity test
the battery must be reconditioned (deep cycled). Please refer to the battery
manufacturer's maintenance manual on how to proceed.
L. SWITCH AC POWER OFF.
Switch the AC on-off/reset switch off before
removing the battery.
NOTE: If in emergency it is required to
stop the test, switch the unit to off/reset.
When the test is restarted the timer is
reset to zero. It may be necessary to
recharge the battery before resuming the
test.
CA-1550 CHARGER / ANALYZER - OPERATING MANUAL V1.2