2 Flue and Ventilation
2.5 Boilers in a Compartment
Where the installation of the boiler will be in an unusual position,
special requirements are needed, the current issue of BS6798
gives detailed guidance on these requirements.
A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose. An existing
cupboard or compartment modified for the purpose may be
used. Details of essential requirements for cupboard or
compartment design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for
easy removal of the boiler.
Where the boiler is fitted in a cupboard or compartment,
permanent high and low level ventilation must be provided. The
minimum ventilation areas required are given in Table 3.
2.6 Timber Frame Building
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.
Diagram 2.1
A
DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING
300
B
BELOW GUTTER, DRIAN/SOIL PIPE
300
C
BELOW EAVES
300
D
BELOW A BALCONY OR CAR PORT
600
E
FROM VERTICAL DRAIN PIPES AND
SOIL PIPES
75
F
FROM INTERNAL OR EXTERNAL
CORNERS
250
G
ABOVE ADJACENT GROUND OR
BALCONY LEVEL
300
H
FROM A SURFACE FACING THE
TERMINAL
600
I
FACING TERMINALS
600
J
FROM OPENING (DOOR/WINDOW) IN
CAR PORT INTO DWELLING
1200
K
VERTICAL FROM A TERMINAL
1500
L
HORIZONTALLY FROM A TERMINAL
300
MINIMUM
POSITION
SPACING (mm)
MINIMUM SITING DIMENSIONS FORBALANCED FLUE
TERMINALS
3815A
Under Car Port etc.
H,I
J
D
F
K
A
A
F
G
E
A
G
G
B,C
B,C
F
F
K
K
K
C
L
L
G
G
FROM
OUTSIDE
COMPARTMENT AIR VENT TABLE
COMPARTMENT
VENTILATION
REQUIREMENTS
83cm
2
12.5in
2
83cm
2
12.5in
2
VENTILATION
FROM ROOM
OR SPACE
165cm
2
25in
2
165cm
2
25in
2
HIGH LEVEL
LOW LEVEL
VENT AREA
VENT AREA