7 - Error handling

7.1 Freeze Protection
Frost protection function for cascade relates to system

sensor temperature. When system sensor value is below

10°C (50°F), internal and CH pump of managing boiler

start. Display shows “freeze protection”.

When there is CH call for heat, freeze protection will be

overridden and control will start for CH.

Managing Boiler

• Once cascade freeze protection is activated managing

boiler will operate as individual boiler in freeze

protection mode.

• If boiler supply temperature drops below 5°C

(41°F) burner starts at minimum fi ring derate and

continues fi ring until lowest of both supply and return

temperatures are above 15°C (59°F).

• After burner is switched off, internal and CH pumps run

for post purge period.

Dependent Boiler

• If supply temperature of dependent boiler drops below

freeze protection function, this boiler also starts and will

operate like individual boiler.

7.2 Emergency Mode

Open/Shorted System Sensor

• When system sensor is open or shorted all boilers

will go to permanent heat demand operation and use

Emergensy Setpoint.

• Managing boiler display shows “EMERGENCY MODE” and

system sensor error.

• Emergency mode is default active for each boiler,

however individual boiler can be switched off via “Permit

Boiler Emergency Mode” setting in User Menu of effected

boiler. When not permitted only freeze protection is

active.

Loss Of Cascade Communication

• Loss of cascade communication is detected by

dependent boilers.

• Individual boilers will show error on display when

communication is lost.

• Boiler will go to permanent heat demand operation and

use Cascade Setpoint.

• Set parameter per boiler.

Managing boiler error
When managing boiler is in error mode this boiler is not

used anymore for cascade system. However dependent on

error code pumps connected by managing boiler still can be

controlled for cascade system.

Cascade system can NOT operate with following errors:

A04 - Gas valve relay error,
A05 - Safety relay error
E27 - Water pressure error,
E31 - Low water cutoff.

MULTIPLE BOILER GUIDE