Control Installation & Setup
Problem Solving
THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.
FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE REFER
TO THE END OF THESE INSTRUCTIONS
PROBLEM
PROBABLE CAUSE
REMEDY
a Black – out
a
Wait
b Tripped Circuit Breaker
b
Reset
c Blown Fuse
c
Replace
Unit fails to
start
d Electrical Fault
d
Call Climate Technologies Service Provider
a Pump Seized
a
Isolate power and then take off top of pump
and try to free it. Some lubricant may help.
Pump fails
to start
b Pump Burnt Out
b
Call Climate Technologies Service Provider
a Float Valve Leaking
a
Check adjustment or replace seal
Water
leaking
from
overflow
b Drain from Celdek Pads
b
Normal Operation
a Loose Delivery Tube
a
Check and tighten
b Break in tubing
b
Replace as necessary
Water
Droplets in
air stream
c Pump Delivers Excessive Water to
Pads
c
Adjust the Dialflo to reduce the flow
a Inadequate Exhaust
a
Provide more open area to exhaust stale air
Excessive
humidity
b Outside humidity high
b
Turn pump off.
a Dirty Filters
a
Clean
b Dry Filters
b
Check water delivery system. Adjust if
necessary.
Inadequate
Cooling
c Dialflo not set correctly
c
Adjust Dialflo so that the pads have even
saturation.
a Unit located near odor source
a
Remove source
Unpleasant
Odor
b New Celdek filter smell
b
Smell will disappear after a period of
operation.
Rapid
formation of
white
deposits on
pads
High Mineral Content
Bleed off should be set at maximum. More
regular maintenance may be required.