Vertical vent installation, Vertical vent installation interior chase, Uilt – Dansons V-50 User Manual
Page 22: Nsert, Nstallation
Can
adian Comfort Industries V05
22
VULCAN “V” SERIES OWNERS MANUAL
Copyright 2005
www.salesunlimited.com
Dansons Group Inc.
B
UILT
-I
N
I
NSERT
I
NSTALLATION
.
.
.
CON
’
T
PELLET VENT MUST MAINTAIN A MINIMUM 3” CLEARANCE TO ANY COMBUSTIBLE (INSTALL
VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER).
DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR STOVE.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
Figure 28
These examples show two styles of vertical install.
These require Spacer Kit # ACI-3VL.
The framed openings for these installations need to be:
Tradition Bay View
Height 21”
21 - 25”
Width 28 ¼”
30”
Depth 18”
17”
If constructing a chase, adequate, insulation, vapor barrier, drywall, and caulking must be used.
18”
8”
6”
Wall Band /
Support Brkt
every 5’
Wood Frame
Construction
Ceiling Support /
Firestop Spacer
Stand Off
Part ACISOVL
3” minimum
air gap
Vertical Vent Installation
18”
8”
6”
Wall Band /
Support Brkt
every 5’
Wood Frame
Construction
Ceiling Support /
Firestop Spacer
Stand Off
Part ACISOVL
3” minimum
air gap
Vertical Vent Installation
Interior
Chase
2’
Metal
Chase Cap
Storm Collar
Rain Cap
Clean Out Tee
Clean Out Tee
10’
2’
Shroud
Wood Surround
Wood Surround
Shroud