ADLINK ND-6530 User Manual
Page 79

NuDAM-6521
• 75
@Example
User command:
~300
Response:
!3000$#%@~*
Command leading code setting is $#%@~* for module address ID 30, current
status is factory default setting.
5.4.19 Change Command Leading Code Setting
@Description
User can use this command to change command leading code setting as he
desired.
@Syntax
~(Addr)10(C1)(C2)(C3)(C4)(C5)(C6)
~
Command leading code.
(Addr)
Address ID, range (00 - FF).
10
Change command leading code setting.
(C1)
Leading code 1, for read configuration status, firmware version,
etc. default is $. (1-character)
(C2)
Leading code 2, for read synchronize sampling, digital
output ,default is #. (1-character)
(C3)
Leading code 3, for change configuration.
default is %. (1-character)
(C4)
Leading code 4, for read alarm status, enable alarm, etc. default is
@. (1-character)
(C5)
Leading code 5, for read command leading code, change leading
code, etc. default is ~.
(1-character)
(C6)
Leading code 6, this leading code is reserved. default is *.
(1-character)
@Response
!(Addr)< CR>
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.