beautypg.com

24 introduction – ADLINK EOS-1200 User Manual

Page 36

background image

24

Introduction

Reducing DI channel Forward Current for High Voltage

As input voltage increases above 5 V, the input current drawn
by the EOS-1200 (forward current If) rises commensurately. At
24 V, for example, current per line is determined by the for-
mula:

(24V- 0.5V)/2.4Kohm = 9.79 mA

Computer

Ground

10 k

Ÿ

+3.3V

Digital Logic

Isolated

Ground

L

oad

2.4 k

Ÿ

EOS-1200

DI

ISO_COM

Supply