1.2 Applications
•
Industrial ON/OFF control
•
External high power relay driving and signal switching
• Laboratory
automation
• Industrial
automation
•
Switch contact status sensing
•
Limit switch monitoring
•
Cooperating with other modules such as A/D and D/A peripherals to
implement a data acquisition and control system
1.3 Specifications
Relay Output
•
Number of cross-points: 32 (2-wire)
•
Relay type: DPDT (2 Form C), non-latching
• Switching
capacity:
•
Max. switching current: 2A
•
Max. switching voltage: 220V
DC
, 125V
AC
•
Max. switching power: 60VA, 60W
•
Failure rate: 10µA, 10mV
DC
•
Contact resistance: 100mΩ max.
•
Relay set/reset time
•
Operate time: 4ms max.
•
Release time: 4ms max.
•
Bounce time: 1ms max.
• Expected
life:
•
Mechanical life: 10
8
operations min.
•
Electrical life: 10
5
operations min. (2A @ 30V
DC
, resistive load)
•
Data transfer: Programmed I/O
Auxiliary Digital I/O
•
Numbers of channel: 8 inputs/outputs
•
Compatibility: 3.3 V/TTL (5V tolerant)
•
Data transfers: programmed I/O
Handshaking Signals
• Programmable
polarity
•
Logic level: 3.3 V/TTL (5V tolerant)
•
Trigger In source: AUX1, PXI trigger bus, PXI star trigger in
•
Scanner Advanced destination: AUX0, PXI trigger bus, PXI star trigger
out
Safety functions