Technical specifications – Denso CLASSIC PLUS 26 User Manual
Page 24
18
TECHNICAL SPECIFICATIONS
MODEL
ITEM/FEATURES
Classic Plus 14
Classic Plus 26
Rating Conditions
dry bulb
95
o
F (35
o
C)
95
o
F (35
o
C)
wet bulb
83
o
F (28.3
o
C)
83
o
F (28.3
o
C)
humidity
(60%)
(60%)
Specifications
power frequency
60Hz
60Hz
line voltage, single phase
115 V
208/230V
power consumption
1.41 Kw
3.37/3.24 Kw
current consumption
12.3 Amps
16.8/14.6 Amps
power factor
95%
97%
starting current
32A
62A
power cord
14 (3-core) AWG
12 (3-core) AWG
Cooling Unit
cooling capability
3,300 Kcal/hr
6,500 Kcal/hr
13,200 BTU/hr
26,000 Btu/hr
cooling system
direct expansion
direct expansion
Blower
type of fan
centrifugal fan
centrifugal fan
air volume: Evaporator (high speed)
470 ft
3
/min;798 m
3
/h
708 ft
3
/min; 1202 m
3
/h
Condenser (high speed)
882 ft
3
/min;1498 m
3
/h
1680 ft
3
/min; 2853 m
3
/h
motor output: (high speed)
0.24 Kw
.59/.63 Kw
(low speed)
0.19 Kw
.54/.56 Kw
Compressor
type
rotary
hermetic scroll
output
0.8 Kw
1.6kw
refrigerant type
R-22
R-22
refrigerant capacity
1.50 lbs (0.68 kg)
1.87 lbs. (0.85 kg)
Safety Devices
compressor overload protector
included
included
fan motor protector
included
included
anti-freezing thermistor
included
included
full drain tank switch
included
included
automatic restart (power interruption)
included
included
compressor time delay program
included
included
Dimensions & Weight
W x D x H (in.)
19.4 x 26.5 x 41.5
19.4 x 28.7 x 47.2
W x D x H (mm)
492 x 673 x 1054
492 x 730 x 1200
weight (lbs/kg)
165/75
235/107
Operating Conditions
inlet air (relative humidity)
113
o
F (45
o
C), < 50%
113
o
F (45
o
C), < 50%
70
o
F (21.1
o
C), > 50%
70
o
F (21.1
o
C), > 50%
Control Device
temperature control
included
included
two speed fan
included
included