COMPONENT INFORMATION

Chilled Water Coil

Chilled Fan Motor

(2) 1/2 HP

Area

Sq. Ft.

7.92

Voltage (Std)

208/230-60-1

Height X Width

Inches

30 X 38

Speed

RPM

1075

Tube OD

Inches

1/2

Full Load Amps

3.6

Rows

3

Locked Rotor Amps

10.5

Fins

12/In. Flat

Fan Diameter

Inches

(2) 22.12

Pattern

1.25 X 1.08 Stag.

Chilled Water Pump

Circuits

9

HP & Service Factor

1/3 - 1.75

Blower Wheels

No.

2

Voltage

208/230-60-1

Diameter x Width

Inches

12-5/8 X 12-5/8

Speed

RPM

3450

Blower Motor (Std)

HP & SF

1 X 1.25

Frame

48

Speed

RPM

3450

Full Load Amps

3.6

Frame

56

Locked Rotor Amps

23.0

Rotation

ccw

Solution Pump Motor

Voltage (Std)

208-230-60-1

HP & Service Factor

3/4 - 1.25

Full Load Amps

6.7

Voltage

208/230-60-1

Locked Rotor Amps

35

Speed

RPM

1725

Blower Motor Pulley

Inches

PD 2.9 - 1.9

Frame

55

Blower Pulley

Inches

PD 12

Full Load Amps

5.4

Belt Length x Width

Inches

51 X 1/2

Locked Rotor Amps

29.5

Filters

(4) 25 X 20 X 1

Pump Pulley Diameter

Inches

7.84

Motor Pulley Diameter

Inches

2.3

Belt Length x Width

36.42 X 3/16

DETAILED COOLING CAPACITIES

AIR ENTERING

C.W. COIL

CHILLER ENTERING AIR TEMPERATURE ° F

85

95

105

CFM

EWB

Capacity

Btuh

X

1000

Capacity

Btuh

X

1000

Capacity

Btuh

X

1000

Total

Sensible

Total

Sensible

Total

Sensible

71

93.5

48.1

92.0

47.5

87.0

45.6

2,500

67

89.5

57.8

88.0

57.2

83.5

55.6

63

81.5

65.9

79.3

65.1

75.0

63.2

71

93.6

50.2

92.1

49.9

87.1

48.3

3,000

67

92.5

62.5

90.0

61.6

85.7

59.9

63

85.5

72.3

83.7

71.6

79.5

70.0

71

93.7

52.5

92.2

52.2

87.2

50.7

3,500

67

93.0

66.2

91.0

65.4

86.0

63.9

63

87.5

77.9

85.7

77.1

81.3

75.6

71

93.8

55.3

92.3

54.4

87.3

53.1

4,000

67

93.4

69.6

91.5

69.1

86.5

67.4

63

89.5

83.4

87.5

82.5

82.5

80.8

Notes:

1. Sensible heat capacities shown are based on 80 F entering air at the evaporator.

2. Direct interpolation is permissible. Do not extrapolate.
3. To interpolate:

(a) below 80 F DB, subtract 800 Btuh per 1000 cfm

for each degree below 80 F from the listed sensible capacity.

(b) above 80 F DB, add 800 Btuh per 1000 cfm

for each degree above 80 F from the listed sensible capacity.

4. Formula:

LDB = EDB -

Sensible Heat Capacity (Btuh)

1.08

X cfm

Total Capacity (Btuh)

4.5

X cfm

where h = Enthalpy (Btu/lb)

Lh - Eh -