beautypg.com

Fire hazard, Fig. #4, Correct incorrect – Maytag 53-3442 User Manual

Page 5: Bottom exhausting, Exhaust venting requirements

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

EXHAUST VENTING REQUIREMENTS

A

WARNING

FIRE HAZARD

NEVER EXHAUST INTO A CHIMNEY, DUCT, GAS
VENT, WALL, CEILING, ATTIC, CONFINED SPACE,

BEDROOM, OR UNDER A BUILDING.

DO NOT USE VINYL, PLASTIC, CLOTH OR OTHER
NONMETALIC DUCT TO EXHAUST THE DRYER.

MULTIPLE INSTALLATIONS REQUIRE INDIVIDUAL
EXHAUST SYSTEMS.

DRYERS

INSTALLED

IN

A

MANUFACTURED

(MOBILE) HOME MUST BE VENTED OUTDOORS.

PERIODICALLY CLEAN LINT FROM VENT SYSTEM.

CLEAN

FREQUENTLY

IF

USING

MAXIMUM

LENGTH OF VENT.

Exhausting can be accomplished directly from the rear of

the cabinet, through right side of the cabinet, or down­
ward through the cabinet base. If your existing ductwork is

plastic, nonmetal, or combustible, replace it with METAL.
Standard four inch diameter galvanized or aluminum pipe
should be used. DO NOT use any pipe which may be sus­
ceptible to rust or COMBUSTION. To avoid catching lint
the crimped end of each pipe section should face away
from the dryer. Do not use screws or other fasteners that
extend into the exhaust pipe or duct.

Flexible 4” diameter metal tubing may be used for
exhausting the dryer. However, the convolutions create a
greater restriction than pipe and serious blockage can

result if the tubing is bent too sharply. If clearance to the
wall is less than 8 inches, use a 4” sheet metal elbow at
the rear of the dryer to avoid a sharp bend in the tubing.

Do not use over 8 feet (2.5 m.) of flexible metallic tubing

between the elbow and the vent hood.

VENT HOOD

The use of a vent hood
on the outside is recom­

mended.

When the dryer stops the damper automatically closes to

prevent drafts and the entrance of insects and rodents. To
avoid restricting the outlet, maintain a minimum 8 inch
clearance between the hood and the ground or other
obstruction.

FIG. #4-

PIPE CONNECTION

EXHAUST FLOW

EXHAUST FLOW

CORRECT _______________ INCORRECT_______

Number of

90° Turns

Separated by

at least 4 ft.

of Straight Run

VENT HOOD TYPE

____________ K

\

. .

^

-----

I

I — 4 "

OPENING

I

I —

OPENING

0

45 feet

30 feet

f

35 feet

20 feet

2

25 feet

10 feet

Vent should never exceed 0.6 inches water column back
pressure, fluff empty dryer.

BOTTOM EXHAUSTING

If space permits behind the dryer, a 4” elbow pointed down­

ward may be used to pass the exhaust system through the
floor. If this is not possible, the dryer may be exhausted
through the bottom as illustrated in FIG. #7. When exhaust­

ing in this manner, the installation should be made accord­
ing to the following steps:

1. Disconnect electric cord.

2. Raise the top of the dryer by pressing in with a putty knife

on the top panel retaining clips. FIG. #5.

Remove front panel by removing two VT screws inside top

corners of front panel. Disconnect door switch wires.

NOTE position of front seal before removing front panel.
Remove the cylinder as follows:

LENGTH OF VENT

Maximum Length of 4” Rigid Duct

a. Force idler pulley to the right and remove cylinder belt

from idler and motor pulleys. See FIG. #6.

b. Lift up and turn cylinder to clear the roller supports.
c. Lift out of cabinet.

5. Remove tape and screw securing dryer vent pipe.
6. Remove the 4” dryer vent pipe and shorten to a suitable

length. Length depends on type of elbow purchased.

7. Remove knockout from dryer base.
8. Place dryer in position and mark duct location on floor.

Check floor joist location before sawing hole in floor.