Table 8 — Fan Performance, 48LJD/LJE/LJF006 Vertical Discharge Units; Standard Motor (Belt)

AIRFLOW

(Cfm)

1500
1600
1700
1800
1900

2000
2100
2200

2300
2400
2500

0.1

0.2

Rpm

Bhp

Rpm

Bhp

750

0.37

808

0.43

794

0.44

846

0.50

839

0.52

884

0.58

885

0.61

924

0.67

932

0.72

965

0.77

979

0 83

1008

0 88

1026

0.96

1051

1 01

1074

1.10

1095

1.15

1122

1 25

1140

1.30

1170

1 42

1185

1.46

1218

1.61

1231

1 64

EXTERNAL STATIC PRESSURE (in. wg)

LEGEND

Bhp — Brake Horsepower

NOTES:
1 Boldface indicates fieid-suppiied drive required. (See Note 6)

2.

indicates field-supplied motor and drive required.

3 Maximum usable bhp is 1.8 Extensive motor and electrical test­

ing on these units ensures that the full horsepower range of the

motor can be utilized with confidence Using your fan motors up
to the horsepower ratings shown will not result in nuisance trip­
ping or premature motor failure. Unit warranty will not be af­
fected.

4. Values include losses for filters, unit casing, and wet coils
5 Use of a field-supplied motor may affect wire sizing. Contact Car­

rier representative to verify.

6 Standard motor drive range is 900 to 1300 rpm. All other rpms

require field-supplied drive.

Table 9 — Fan Performance, 48LJD/LJE/LJF007 Vertical Discharge Units; Standard Motor (Belt)

LEGEND

Bhp — Brake Horsepower

NOTES:
1

Boldface indicates field-supplied drive required (See Note 6)

indicates field-supplied motor and drive required.

Maximum usable bhp is 2 4 Extensive motor and electrical test­

ing on these units ensures that the full horsepower range of the

motor can be utilized with confidence Using your fan motors up
to the horsepower ratings shown will not result in nuisance trip­
ping or premature motor failure. Unit warranty will not be
affected.

4 Values include losses for filters, unit casing, and wet coils.
5 Use of a field-supplied motor may affect wire sizing Contact Car­

rier representative to verify.

6. Standard motor drive range is 1070 to 1460 rpm. All other rpms

require field-supplied drive.