Carrier 48LJD User Manual
Page 17
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 8 — Fan Performance, 48LJD/LJE/LJF006 Vertical Discharge Units; Standard Motor (Belt)
AIRFLOW
(Cfm)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.1
0.2
Rpm
Bhp
Rpm
Bhp
750
0.37
808
0.43
794
0.44
846
0.50
839
0.52
884
0.58
885
0.61
924
0.67
932
0.72
965
0.77
979
0 83
1008
0 88
1026
0.96
1051
1 01
1074
1.10
1095
1.15
1122
1 25
1140
1.30
1170
1 42
1185
1.46
1218
1.61
1231
1 64
EXTERNAL STATIC PRESSURE (in. wg)
LEGEND
Bhp — Brake Horsepower
NOTES:
1 Boldface indicates fieid-suppiied drive required. (See Note 6)
2.
indicates field-supplied motor and drive required.
3 Maximum usable bhp is 1.8 Extensive motor and electrical test
ing on these units ensures that the full horsepower range of the
motor can be utilized with confidence Using your fan motors up
to the horsepower ratings shown will not result in nuisance trip
ping or premature motor failure. Unit warranty will not be af
fected.
4. Values include losses for filters, unit casing, and wet coils
5 Use of a field-supplied motor may affect wire sizing. Contact Car
rier representative to verify.
6 Standard motor drive range is 900 to 1300 rpm. All other rpms
require field-supplied drive.
Table 9 — Fan Performance, 48LJD/LJE/LJF007 Vertical Discharge Units; Standard Motor (Belt)
LEGEND
Bhp — Brake Horsepower
NOTES:
1
Boldface indicates field-supplied drive required (See Note 6)
indicates field-supplied motor and drive required.
Maximum usable bhp is 2 4 Extensive motor and electrical test
ing on these units ensures that the full horsepower range of the
motor can be utilized with confidence Using your fan motors up
to the horsepower ratings shown will not result in nuisance trip
ping or premature motor failure. Unit warranty will not be
affected.
4 Values include losses for filters, unit casing, and wet coils.
5 Use of a field-supplied motor may affect wire sizing Contact Car
rier representative to verify.
6. Standard motor drive range is 1070 to 1460 rpm. All other rpms
require field-supplied drive.
17