Power source availability signal contacts, Programmable engine–generator exerciser – Winco ASCO 300 Accessory 11BG User Manual
Page 2

381339–252 B
ASCO POWER TECHNOLOGIES L.P.
50 Hanover Road, Florham Park, New Jersey 07932 USA
www.asco.com
page 2
2–line
display
3 buttons
connections
for power source
availability
signal contacts
J3
J1
9
wiring
J1
Figure 4. Accessory 11BG module (mounted behind operator interface and connected to the controller)
includes power source availability signal contacts and a programmable engine exerciser.
Power Source Availability Signal Contacts
The module provides one Form C contact each for the
normal and emergency power sources to signal the
acceptability of the source as sensed by the controller. The
signal contacts operate in conjunction with the Source
Available lights on the operator interface. Field wiring
terminals are provided as shown in Figure 5 and the wiring
diagram.
Contact ratings:
2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive
Figure 5. Power source availability signal contacts.
Programmable Engine–Generator Exerciser
Note: Refer to your Series 300 ATS Operator’s Manual
to set DIP switches S1 & S2 in the Group 1 Controller.
A backup battery in the Series 300 ATS Group 1 Controller
(see Operator’s Manual, Sections 4 and 5) must be turned
on to maintain the settings and to allow programming with
the normal and emergency power sources turned off.
The Acc. 11BG module includes a programmable genera-
tor exerciser that provides for weekly or biweekly opera-
tion. The exerciser may have to be turned on (enabled) by
setting S1 DIP switch actuator 7 to OFF (left position), and
S2 DIP switch actuator 5 to OFF (left position).
The programmable engine–generator exerciser incorpo-
rates a 7–day or 14–day time base. Proper Group 1
Controller settings must be made to determine whether or
not the test will be done with or without load transfer
(S1 DIP switch actuator 8).
See next page for instructions on setting the exerciser.
S1 DIP Switch Settings
in Series 300 ATS Group 1 Controller
Programmable
Exerciser
Function
ACTUATORS 7 & 8
OFF ON
Enabled &
Exercise
without Load
Actuator 7 OFF
Actuator 8 OFF
7
EXER ACTV
8
LOAD
Enabled &
Exercise
with Load
Actuator 7 OFF
Actuator 8 ON
7
8
EXER ACTV
LOAD
S2 DIP Switch Settings
in Series 300 ATS Group 1 Controller
Programmable
Exerciser
Function
ACTUATOR 5
OFF ON
Enabled
Actuator 5 OFF
5
EXT EXER
Disabled
Actuator 5 ON
5
EXT EXER
Shaded DIP switches are standard factory settings.