Specifications – Winco PSS40LS/C User Manual

Page 6

background image

Page 4

7263-00

60706-188

J - Reset Push-button. This button is pressed to cancel a
settings editing session and discard any settings changes. When
pressed, this button also resets the Breaker Management Pre-
Alarms

K - Arrow Push-buttons. These four buttons are used to
navigate through the front panel display menus and modify
settings. The left- and right-arrow buttons are used to navigate
through the menu levels. The right arrow button is pressed to
move downward through the menu levels and the left-arrow
button is pressed to move upward. Within a level, the up-arrow
and down-arrow buttons are used to move among items within
the menu level. Pressing the down-arrow button moves to items
lower in the list. Pressing the up-arrow button moves to items
higher in the list. During a settings editing session, the up- and
down-arrow buttons are used to raise and lower the value of the
selected setting.

L - Edit Push-button. Pressing this button starts an editing
session and enables changes to the DGC-2020 settings. At the
conclusion of an editing session, the Edit push-button is pressed
again to save the setting changes.

DISPLAY OPERATION

The front panel display is used to make settings changes and
display metering values. Refer to call-outs J, K, and L in text and
illustration for information on changing settings through the front
panel and navigating through the Metering screens. When the
unit is first powered up, the clock may need to be reset. Editing
the clock provides familiarity with the edit process. All program-
ming changes from the front panel are accessed through the edit
key to begin and exit the internal microprocessor program.

Log-in and Permissions

To Log-in, navigate to the SETTINGS, ENTER PASSWORD
screen and press the Edit key. Use the Up/Down arrow keys to
scroll through the characters. Use the Left/Right arrow keys to
enter more characters. The Owner operator password is OP.
Once the password has been entered, press the Edit key to Log-
in. See the key stroke sequence listed below to access the
control and enter the edit mode. A LOGOUT selection now
appears in the list of SETTINGS. To logout, navigate to SET-
TINGS, LOGOUT and press the Edit key. The LOGOUT selection
is removed from the SETTINGS list.

Sequence for setting (or resetting) the system clock -
1)

Press ‘K’ (right key) for initial set or ‘K’ (left to back up, up /

down) to choose menu item and time/date element to be
changed.
2)

Press ‘L’ (Edit) to access change mode to enter Password -

OP as follows:
2a -Press K (up) to select O
2b -Press K (right) to move cursor
2c -Press K (up) to select P
2d -Press L (Edit) to begin change mode
3)

Press ‘K’ (up or down) to choose year

4)

Press ‘L’ (Edit) to enter year

5)

Press ‘K’ (down) to select month mode

6)

Press ‘L’ (Edit) to access month change

7)

Press ‘K’ (up or down) to choose month

8)

Press ‘L’ (Edit) to enter month

9)

Repeat sequence 5 through 8 for day, minute, second and

DST (Daylight Saving Time.
To finish clock setting, process - Press ‘K’ (left).

The microprocessor is still in the General Settings Edit mode.
Pressing ‘K’ (left) a second time exits the Edit mode and allows
full access to the View Only mode for all control settings and
current status. Any items to be changed are accessed by
pressing ‘K’ (up/down/right or left) to select, ‘L’ (Edit) to change
and ‘K’ (left) to exit.

SPECIFICATIONS

GENERATOR

MODEL

WATTS

VOLTS

AMP

HZ

PH

RPM

PSS27LS

27,000

120/240

112.5*

60

1

1800

PSS27LS-4

27,000

120/208

94.0*

60

3

1800

PSS27LS-17

27,000

120/240

81.2*

60

3

1800

PSS27LS-18

27,000

277/480

40.6*

60

3

1800

PSS40LS

40,000

120/240

166.7**

60

1

1800

PSS40LS-4

40,000

120/208

138.9**

60

3

1800

PSS40LS-17

40,000

120/240

120.4**

60

3

1800

PSS40LS-18

40,000

277/480

60.2**

60

3

1800

*Derate 11% for Natural Gas operation. Derate 3.5% per
1000 feet elevation above sea level.
**Derate 7% for LP operation. Derate 3.5% per 1000 feet
elevation above sea level.

FUEL CONSUMPTION

NG (1,000 BTU/CU FT) L.P. VAPOR (2,520 BTU/CU FT)
MODEL

CF/HR

BTU/HR

#/HR GAL/HR CF/HR

BTU/HR

PSS27LS

320

320,000

14.1

3.3

120

302,400

PSS40LS

450

450,000

20.0

4.7

170

428,400

L.P. TANK SIZING

Minimum required L.P. Tank size for L.P. Vapor withdrawal
operating at various outside temperatures given in degrees
Fahrenheit (Celsius)

TANK TEMPERATURE

MODEL

60 F(16 C)

30 F(0 C) 0 F(-18 C)

-20 F(-29 C)

PSS27LS

100 Gal

150 Gal

500 Gal*

1500 Gal*

PSS40LS

160 Gal.

300 Gal.

1000 Gal.*

2000 Gal.*

*Recommend liquid withdrawal at these temperatures.

ENGINE SPECIFICATIONS:

Refer to engine operating and maintenance instructions

** NOTICE **

Regarding Engines - This manual covers the generator portion of
these units. See the separate engine instruction manual for
engine-related problems, detailed engine information and engine
warranty.

** CAUTION **

EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specified in the engine manual.