beautypg.com

Specifications, Unpacking instructions, Generator – Winco PSS25000/A User Manual

Page 5: Fuel consumption, Lp tank sizing, Engine specifications, Unpacking

background image

PAGE 3

5076-10

60706-171

SPECIFICATIONS

GENERATOR

MODEL

WATTS* VOLTS

Pf

AMPS* HZ

pH RPM

PSS25000

25,000

120/240

1.0

104.0

60

1

3600

PSS25000-4

25,000

120/208

.8

86.8

60

3

3600

PSS25000-17 25,000

120/240

.8

75.3

60

3

3600

PSS25000-18 25,000

277/480

.8

36.6

60

3

3600

*Derate 10% for Natural Gas operation. Derate 3.5%
per 1000 feet elevation above sea level.

FUEL CONSUMPTION

NG

LP

1000 BTU/CU FT

2520 BTU/CU FT

MODEL CF/HR

BTU/HR

#/HR GAL/HR

CF/HR BTU/HR

PSS25000* 375

375,000

17.1

4.1

148

375,000

*Based on full load operation

LP TANK SIZING

Required LP Tank size for LP Vapor withdrawal operat-

ing at various outside temperatures given in degrees
Fahrenheit (Celsius)

TANK TEMPERATURE

MODEL

60 f(16 c) 32 f(0 c)

0 f(-18 c) -20 f(-29 c)

PSS25000* 250 Gal.

500 Gal.

500 Gal. 1000 Gal.

* Fuel tank sizes for PSS25000 on liquid withdrawal are
considerably smaller consult your local fuel supplier.

ENGINE SPECIFICATIONS:

Refer to engine operating and maintenance instructions.

** NOTICE **

Regarding Engines - This manual covers the generator
portion of these units. See the separate engine instruc-
tion manual for engine-related problems, detailed engine
information and engine warranty.

** CAUTION **

Be sure to check the engine oil level frequently, as
specified in the engine manual.

The engine manufacturer has established an excellent

worldwide engine service organization; engine service is
available from a nearby authorized dealer or distributor;
check the yellow pages of the telephone directory under
“engines,” or ask the dealer from whom you purchased
the power plant.

The rated power of each engine-generator is limited by

the temperature, altitude and all other ambient conditions
specified by the engine manufacturer. Engine power will
decrease 3-1/2% for each 1000 ft. above sea level, and
will decrease an additional 1% for each 10 degrees
Fahrenheit above 60 degrees Fahrenheit.

UNPACKING INSTRUCTIONS

** NOTICE **

When unpacking the generator set, be sure to inspect it
carefully for freight loss or damage. If loss or damage is
noted at the time of delivery, require that the person
making the delivery make note of the loss or damage on
the freight bill, or affix his signature under the consignor’s
memo of the loss or damage. Contact the carrier for
claim procedures.

When loss or damage is noted after delivery, segregate

the damaged material, and contact the carrier for claim
procedures. Be sure to retain the packaging material for
carrier inspection.

“Concealed Damage” is understood to mean damage

to the contents of a package which is not evident at the
time of delivery by the carrier, but which is discovered
later. The carrier or carriers are responsible for mer-
chandise lost or damaged in transit. The title to goods
rests with the consignee when generators are shipped
F.O.B. factory, and only the consignee can legally file a
claim.

**** CAUTION ****

The PSS25000 is shipped with oil, and a 50/50 mix of
coolant. Be sure to check all fluid levels before operat-
ing. See engine manufacturer’s instruction manual for
recommended oil requirements before initial starting.

UNPACKING:

1.

Carefully remove the carton.

2.

After inspecting the engine-generator and transfer

switch for external physical damage, check for the
following items packed inside the carton.

a. Owner’s manual, wiring diagram and parts list.
b. Engine manufacturer’s instruction manual.

3.

Remove main frame hold down bolts, (4).

4.

Unit can now be lifted from shipping pallet.