The following is an optional way to interconnect the

Generator and the Transfer Switch. The wires termi-

nate on TB7 as follows:

WIRE #

COLOR

TB7 TERMINAL

# 1

White

# 2

# 24

Red

# 4

# 22

Orange

# 7

The following leads are wire nutted together:

WIRE #

COLOR

FROM

# 5

Black

Generator

# 5

Black

TB7 # 3

# 5

Black

TB7 # 5

# 5

Black

TB7 # 8

Fuel line protected and a moisture trap in

stalled (may be required for NG).

LP/NG pressure OK. 4-6 oz. (7- in. WC).

Battery connections clean and tight.

Battery fully charged.

All AC and DC wiring installed and properly

protected.

* Refer to engine owners manual for proper

levels and types.

After completing the above checklist, the engine

generator set is ready for the initial start-up test.

START UP PROCEDURE

Engine Generator Set only

Move the left hand toggle switch from OFF to the

ON position. The alarm light should go out. Next

move the right hand toggle witch from the AUTO to

the RUN position. You should hear the fuel solenoid

engage at this time. Next lift the toggle switch to the

START position and hold. The engine starter should

engage and the engine will start. As soon as the en-

gine starts release the toggle switch and it will return

to the run position. If the engine does not start after

5 seconds release the switch and let the starter rest

for 5 seconds and re-attempt to start. If the unit still

will not start, consult the troubleshooting guide in the

back of this manual.

With the engine running smoothly, check the no load

voltage and frequency at wire # and # 4 (L2 and

L6 in the ASCO ATS) on the generator terminal block

in the ATS. The voltage should be 240 volts plus or

minus nominal. The frequency should be between

6.5 to 62 hertz (Hz). The voltage should also be

checked between the hot terminals (L2 and L6) and

the neutral to be certain of a balanced voltage output

and a solid neutral connection. The voltage should

be about on half of the line to line voltage.

INITIAL START UP

******************

***** WARNING *****

******************

DO NOT jump start these engine generator sets.

Starting these units on a low battery of jump start-

ing them will cause damage to the engine control

module.

Use the following checklist to verify correct in-

stallaion before starting the engine:

Engine oil.* Check level & fill as required with

proper grade/quantity.

Unit mounting base properly bolted down.

Clearance for service and maintenance on all

sides.

Proper fuel line material and size.

All fuel line connections tight.