During operation, Notice – VACUUBRAND PC 3001 basic pro User Manual
Page 30

page 30 of 54
When assembling, ensure
vacuum-tightness. After as-
sembly, check the whole system for leaks.
Secure hose connections at the pump appropriately, e.g.,
with hose clamps, to protect against accidental detach-
ment.
To reduce pump noise emanating from the pump exhaust
port, connect an exhaust hose or use a silencer.
During operation
➨
Vent and dispose of
potentially dangerous gases or
vapors at the outlet of the pump appropriately.
+
Due to the high compression ratio, the pump might
generate overpressure at the outlet. Check pressure
compatibility with system components (e.g., exhaust
tubing or exhaust valve) at the outlet. Ensure that the
pump outlet is neither blocked nor restricted.
+
Maximum ambient temperature: 104 °F (40 °C)
Check the maximum temperatures, if installing the
pump in a cabinet or a housing. Make sure ventilation
is adequate, especially if the ambient temperature is
elevated.
• If the pump is installed at an altitude of more than 6500
ft (2000 m) above mean sea level, check compatibility
with applicable safety requirements, and adopt suit-
able measures. There is a risk of the motor overheat-
ing due to insufficient cooling.
• Check compatibility with the
maximally permitted
pressure at outlet and the maximum pressure dif-
ference between inlet and outlet ports.
Do not start the pump if the
pressure difference between
inlet and outlet ports exceeds max. 16.0 psi (1.1 bar).
Attempts to start the pump at higher pressure difference
may cause stalling and damage of the motor.
NOTICE