beautypg.com

Extension cords, Symbology – Chicago Electric SCREWING TOOL 95065 User Manual

Page 6

background image

SKU 95065

For technical questions, please call 1-800-444-3353

Page 6

Outlets for 2-prong plug

2. Double insulated tools may be used in

either of the 120 volt outlets shown in
the preceding illustration. (See Outlets
for 2-prong plug.)

Extension Cords

Grounded

1.

tools require a three wire

extension cord. Double Insulated
tools can use either a two or three wire
extension cord.

As the distance from the supply outlet

2.

increases, you must use a heavier
gauge extension cord. Using extension
cords with inadequately sized wire
causes a serious drop in voltage,
resulting in loss of power and possible
tool damage. (See Table A.)

The smaller the gauge number of the

3.

wire, the greater the capacity of the
cord. For example, a 14 gauge cord
can carry a higher current than a 16
gauge cord. (See Table A.)

When using more than one extension

4.

cord to make up the total length, make
sure each cord contains at least the
minimum wire size required. (See
Table A.)

If you are using one extension cord for

5.

more than one tool, add the nameplate
amperes and use the sum to determine
the required minimum cord size. (See
Table A.)

If you are using an extension cord

6.

outdoors, make sure it is marked with

the suffix “W-A” (“W” in Canada) to
indicate it is acceptable for outdoor use.

Make sure the extension cord is

7.

properly wired and in good electrical
condition. Always replace a damaged
extension cord or have it repaired by a

qualified electrician before using it.

Protect the extension cords from sharp

8.

objects, excessive heat, and damp or
wet areas.

RECOMMEnDED MInIMuM WIRE

GAuGE FOR EXTEnSIOn CORDS*

(120/240 VOLT)

nAMEpLATE

AMpERES

(at full load)

EXTEnSIOn CORD

LEnGTH

25’

50’

75’

100’

150’

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

TABLE A

* Based on limiting the line

voltage drop to five volts at
150% of the rated amperes.

Symbology

Double Insulated

Canadian Standards
Association

Underwriters Laboratories, Inc.

V~

Volts Alternating Current

A

Amperes

n0 xxxx/min.

No Load Revolutions per
Minute (RPM)