"OPEN TO LEFT" ADJUSTMENT PROCEDURES

Left Gate Motion Adjustment (R160)
1. Initiate opening the gate.
2. Wait 4 to 5 seconds, then lightly "tug"against the edge of the gate to simulate an obstacle.
3. If the gate does not stop, reclose the gate and adjust the pot slightly counterclockwise.
4. Repeat steps 1-3 until the gate stops when tugged and has the desired sensitivity.
Right Gate Motion Adjustment (R69)
1. Open the gate fully, then initiate closing the gate.
2. Wait 4 to 5 seconds, then lightly "bump" the leading edge of the gate to simulate an obstacle.
3. If the gate does notstop or back up, reopen the gate and adjust the pot slightly

counterclockwise.

4. Repeat steps 1-3 until the gate stops or backs up when bumped and has the desired

sensitivity.

INRUSH CURRENT ADJUSTMENT (R203)

1. Turn the pot fully counterclockwise.
2. Open the gate.
3. If the gate stops due to a fault condition, slightly adjust the pot clockwise.
4. Repeat steps 2 and 3 until the gate cycles without a fault.
5. Open gate fully, then iInitiate closing the gate.
6. If the gate stops or backs up due to a fault condition, slightly adjust the pot clockwise.
7. Repeat steps 6 and 7 until the gate cycles without a fault and has the desired sensitivity.

I. BASIC GATE OPERATOR PROGRAMMING

Even if you plan to program the gate operator by telephone, you may want to enter some immediate
instructions during installation. The following list of instructions will help you set basic controls so the
gate will operate properly until you have time for full programming, either directly or by telephone. For
complete programming instructions, refer to the enclosed manual “Programming Instructions For The
LiftMaster SL 1000-X1 and SW 2000-X1 Gate Operators” (Doc. No. 6001193).

To access programming mode: enter

∗∗∗ 000000 (3 asterisks, 6 zeroes)

To program a command: a) enter step number b) enter required digits of data c) enter # (pound sign)
To exit programming mode: enter 00# (2 zeroes, 1 pound sign)

Step

Purpose

Required Digits

Acceptable Input

01 Gate

Type

1

0 - 1 (0 = Slide, 1 = Swing)

06 Anti-Tailgate Enable (ATG)

1

0 - 1 (0 = Disabled, 1 = Enabled)

08

Reclose Time (RT)

Up to 3

0 - 250, expressed in seconds
(0 = Disabled)

09 Maximum

Retry Count

1

0 - 2 (0 = Do not retry)

10 Retry Pause Time

Up to 2

30 - 99, expressed in seconds

11

Reverse Sense Backup Inches

Up to 3

0 - 499, expressed in inches

13 Safety Bar Backup If Closing

Up to 3

0 - 499, expressed in inches

14 Safety Bar Backup If Opening

Up to 3

0 - 499, expressed in inches

15 Return

Factory Set Defaults

6

101010