beautypg.com

Mechanical – Shellab SMI39-2 User Manual

Page 13

background image

13

3/ Check connections to sensor.
4/ Check calibration

– using independent thermometer, follow

instructions in section 5.6.

Unit will not heat up at all

1/ Verify that controller is asking for heat by looking for HEATING light

if pilot light is not on continuously during initial start up, there is a
problem with the controller.
2/ Check amperage

– amperage should be virtually at maximum rated

(data plate) amperage.
3/ Do all controller functions work?
4/ Is the Overtemperature set high enough?

– for diagnostics, should be

fully clockwise with the pilot light never on.
5/ Has the fuse/circuit breaker blown?

Indicated chamber temperature unstable

1/ ±0.1 may be normal.
2/ Is fan working?

– remove top panel and verify movement of cooling

fan.
3/ Is ambient radically changing

– either door opening or room airflow

from heaters or air conditioning?

– stabilize ambient conditions.

4/ Sensor miss-located, damaged or wires may be damaged - check
mounts for control and Overtemperature sensors, then trace wires or
tubing between sensors and controls.
5/ Calibration sensitivity

– call Customer Service.

6/ Overtemperature set too low

– be sure that its setting is more than 5

degrees over desired set point; check if pilot light is on continuously;
turn controller knob completely clockwise to see if problem solved then
follow instructions in section 5.7 for correct setting.
7/ Electrical noise

– remove nearby sources of RFI including motors,

arcing relays or radio transmitters.
8/ Bad connection on temperature sensor or faulty sensor

– check

connectors for continuity and mechanical soundness while watching
display for erratic behavior; check sensor and wiring for mechanical
damage.
9/ Bad connections

– check connectors for mechanical soundness and

look for corrosion around terminals or signs of arcing or other visible
deterioration.

Will not maintain set point

1/ Assure that set point is at least 5 degrees over ambient.
2/ See if ambient is fluctuating

– check for adjacent open doors or

HVAC duct openings, stabilize ambient conditions.

Display and reference thermometer don’t
match

1/ Calibration error

– see section 5.6.

2/ Temperature sensor failure

– evaluate if pilot light is operating

correctly.
3/ Controller failure

– evaluate if pilot light is operating correctly.

4/ Allow at least 24 hours to stabilize at set point temperature.
5/ Verify that reference thermometer is certified.

Can't adjust set points or calibration

1/ Turn entire unit off and on to reset.
2/ If repeatedly happens, call Customer Service.

Calibrated at one temperature, but not at
another

This can be a normal condition when operating temperature varies
widely. For maximum accuracy, calibration should be done at or as
close to the set point temperature as possible.

MECHANICAL

Door not sealing

1/ Check physical condition of gasket.

This manual is related to the following products: