6/12 Volt - 5 Amp SLA
SOLAR BATTERY CHARGE CONTROLLER
Part No. 1950-136
CSA Certifi ed
Class 1 Div 2 Hazardous Locations
Document Rev. 140304
Recommended Installation Instructions
DO NOT CONNECT OR DISCONNECT WIRING IN A HAZARDOUS ENVIRONMENT!
1. Securely mount the 1950-136 5A SLA Solar Battery Charge Controller in an
approved enclosure near the battery to be charged. The charge controller may
be bolted to a back plate using the available mounting flanges, or an approved
adhesive may be used to attach the charge controller to an available flat surface.
2. Run wire from the charge controller’s terminals to the battery. 18 gauge wire is
recommended if the solar panel provides 1 Amp or less charging current, or 14 gauge
wire if it provides more than 1 Amp of charging current. Strip the wire back 3 mm
(~1/8”) and insert the bare portion into the terminal, then tighten the screw until it
crimps down securely on the wire. An approved in-line fuse holder should be wired
in series between +BAT terminal of the charge controller and the positive terminal of
the battery. A 5 Amp fast-blow style fuse is recommended for circuit protection. If
the battery terminals are connected backwards the LED on the charge controller will
light indicating reversed wiring, and the charge controller will not charge the battery.
3. Run cable from the solar panel through the bottom of the enclosure or provided cable
entrance to the +IN and GND terminals on the charge controller. Strip the wire back 3 mm
(~1/8”) and insert the bare portion into the terminal, then tighten the screw until it crimps
down securely on the wire. If the battery enclosure is located in a potentially hazardous area,
ensure use of conduit or approved cable, and properly seal all wiring entrances as required.
Made in the U.S.A