Rogue Engineering Rhino-10C User Manual
Solar battery charge controller, Charging ahead
Charging Ahead
Rogue Engineering Inc.
3860 S. Jason Street
Englewood Colorado 80110
1-800-364-0659 (Toll Free) 1-303-734-0706 (Phone)
1-303-734-0517 (Fax) www.rogue-engr.com
[email protected] or [email protected]
Rhino- 10C, 12/24 Volt - 10A
SOLAR BATTERY CHARGE
CONTROLLER
With Modbus Serial Communications
and I/O Module Support
Part No. 1950-229
Document Rev. 120705
Designed and Manufactured by
Rogue Engineering Inc.
in Englewood, Colorado, U.S.A.
Function 3 Registers
Function 6 Registers
Register Name
Description
0
Modbus Address Set by sending broadcast message to Modbus Address
0, Register 0, value you desire the address to be
3
Battery Type
0 = SLA, 1 = Flooded; see user manual for charging
voltages based on battery type
4
I/O Direction
0 = input (default), 1 = output
5
Low Voltage
Disconnect
in millivolts; NOTE: If disconnect or reconnect voltages
are set too close, they will be adjusted automatically.
Set either to zero for defaults.
6
Low Voltage
Reconnect
in millivolts; see NOTE for Low Voltage Disconnect
7
Baud Rate
One of 9600, 19200 (default), 57600
8
Turnaround Time 0 (default) through 2000 millisecond response delay
104
I/O
0 = output idle, 1 = output active; this can be written if
I/O direction is set to output
Register Name
Description
0
Modbus Address supports one or two byte address
1
Firmware Version Firmware Version
2
Firmware
Revision
Firmware Revision
3
Battery Type
0 = SLA (default), 1 = Flooded
4
I/O Direction
0 = input (default), 1 = output
5
Low Voltage
Disconnect
in millivolts, default = 10000 for 12V battery,
20000 for 24V battery
6
Low Voltage
Reconnect
in millivolts, default = 12000 for 12V battery,
24000 for 24V battery
7
Baud Rate
One of 9600, 19200 (default), 57600
8
Turnaround Time 0 (default) through 2000 millisecond response
delay
9
Serial Number
Read only
100
Battery Voltage
in millivolts, i.e., 25 volts reads as 25000
101
Solar Voltage
in millivolts
102
Load Current
in milliamps
103
Temperature
degrees C, plus 100, i.e., 25 degrees reads as 125
104
I/O
0 = I/O idle, 1 = I/O active