beautypg.com

Step 10—environmental power products, Vax 7000 system diagram – Compaq 810 User Manual

Page 8

background image

VAX 7000 Model 810

4.38 VAX Systems

Step 10—Environmental Power Products

Power Configuration Table

Options

EPU Values
System
Cabinet
Options

Quantity

Total
EPU
(Quantity
times EPU)

EPU Values
Expansion
Cabinet
Options

Quantity

Total
EPU
(Quantity
times EPU)

Base System includes power regulator, I/O port
module, CPU module, memory module, XMI
I/O channel, DEMNA

30

1

30

I/O expansion cabinet (H9F00-BA/BB/BC)
includes power regulator

0

1

0

Additional CPU modules

7

MS7AA-BA 128 MB of memory

10

MS7AA-CA 256 MB of memory

10

MS7AA-DA 512 MB of memory

10

MS7AA-FA 2 GB of memory

10

CIXCD-AC XMI CI controller

4

4

DEMFA-AA XMI FDDI adapter

5

5

DEMNA-M XMI Ethernet controller

3

3

DWLMA-AA XMI plug-in unit

4

DWLMA-BA XMI plug-in unit

4

KFMSA-BA XMI DSSI adapter

3

3

DMB32-M VAXBI multifunction controller

3

3

DWMBB-LA VAXBI plug-in unit

4

4

RZ26, RZ28, RZ29 SCSI disk drives

1

1

TLZ09 SCSI DAT tape drive

1

1

TZ87-VA SCSI tape drive

3

3

Total the Last Column

1

1.

If EPU is greater then 80, order second power regulator (H7263-AA/AB). EPU must not exceed a system total of 180.

Five and six processor systems include two power regulators, providing a total of 180 EPUs.

Note: Depending on the configuration, the system offers integral UPS capability that supports all in cabinet components

for up to 11 minutes. If UPS support is required for external devices, e.g., console terminals, terminal servers,
printers, modems, etc., a universal UPS can be ordered separately.